III. Unit Start-Up (cont)
COMPONENT TEST
USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY 'DISP'.
PRESS ENTER AGAIN TO DISPLAY 'TEST' FOLLOWED BY 'OFF'. PRESS ENTER TO STOP DISPLAY AT
'OFF' AND ENTER AGAIN SO 'OFF' DISPLAY FLASHES. 'PASS' AND 'WORD' WILL FLASH IF PASSWORD
NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR
EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD.
AT FLASHING 'OFF' DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY 'ON' AND PRESS ENTER. ALL LED
SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO
RETURN TO THE 'DISP' DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLU-
MINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY 'TEST'. PRESS ENTER TO STOP DISPLAY
AT 'OFF' AND ENTER AGAIN SO 'OFF' FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE
THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS 'TEST' 'ON'. REFER TO THE TABLE
BELOW.
KEYPAD
SUB-MODE
ENTRY
ENTER
TEST
ENTER
OUTS
ENTER
CMPA
ENTER
CMPB
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Copyright 2010 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300067-01
Service Test Mode and Sub-Mode Directory
ITEM
DISPLAY
EXPANSION
ON/OFF
SERVICE TEST MODE
OUTPUTS AND PUMPS
FAN1
ON/OFF
FAN 1 RELAY
FAN2
ON/OFF
FAN 2 RELAY
FAN3
ON/OFF
FAN 3 RELAY
FAN4
ON/OFF
FAN 4 RELAY
FAN5
ON/OFF
FAN 5 RELAY
FAN6
ON/OFF
FAN 6 RELAY
V.HPA
XXX%
VAR HEAD PRESS %
V.HPB
XXX%
VAR HEAD PRESS %
CLP.1
ON/OFF
COOLER PUMP 1 RELAY
CLP.2
ON/OFF
COOLER PUMP 2 RELAY
CL.HT
ON/OFF
COOLER/PUMP HEATER
RMT.A
ON/OFF
REMOTE ALARM RELAY
CIRCUIT A COMPRESSOR TEST
CC.A1
ON/OFF
COMPRESSOR A1 RELAY
UL.TM
0 to 15
COMP A1 UnLOAD TIME
CC.A2
ON/OFF
COMPRESSOR A2 RELAY
CC.A3
ON/OFF
COMPRESSOR A3 RELAY
CC.A4
ON/OFF
COMPRESSOR A4 RELAY
MLV
ON/OFF
MINIMUM LOAD VALVE RELAY
CIRCUIT B COMPRESSOR TEST
CC.B1
ON/OFF
COMPRESSOR B1 RELAY
CC.B2
ON/OFF
COMPRESSOR B2 RELAY
CC.B3
ON/OFF
COMPRESSOR B3 RELAY
CC.B4
ON/OFF
COMPRESSOR B4 RELAY
Printed in U.S.A.
ITEM
To Enable Service Test Mode,
move Enable/Off/Remote
Contact switch to OFF. Change
TEST to ON. Move switch to
ENABLE.
Condenser fan contactor 1
Condenser fan contactor 2
Condenser fan contactor 3
Condenser fan contactor 4
Condenser fan contactor 5
Condenser fan contactor 6
Form 30RAP-2T
Pg CL-10
Completed
COMMENT
(Yes/No)
See Note
See Note
See Note
See Note
12-10
Replaces: 30RAP-1T