APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
POINT DESCRIPTION
Percent Total Capacity
Percent Total Capacity
Percent Total Capacity
Pump 1 Maintenance Done
Pump 1 Run Hours
Pump 1 Service Countdown
Pump 2 Maintenance Done
Pump 2 Run Hours
Pump 2 Service Countdown
Pump Changeover Hours
Pump Off Delay Time
Pump Service Interval
Ramp Load Limited
Requested Stage
Rotate Cooler Pumps Now
Saturated Condensing Tmp
Saturated Condensing Tmp
Saturated Suction Temp
Saturated Suction Temp
Slow Change Override
Space Temperature
Storing ICE
Strainer Maint. Done
Strainer Srvc Countdown
Strainer Srvc Interval
Suction Pressure
Suction Pressure
Suction Superheat Temp
Suction Superheat Temp
System Cooling Demand
Level
System Demand Limiting
Temperature Reset
Timed Override In Effect
User Defined Analog 1
User Defined Analog 2
User Defined Analog 3
User Defined Analog 4
User Defined Analog 5
User Defined Binary 1
User Defined Binary 2
User Defined Binary 3
User Defined Binary 4
User Defined Binary 5
Var Head Press Output
WSM Controlling Chiller
LEGEND
R
— Read
W
— Write
Table G — Network Points List (cont)
READ/
POINT NAME
UNITS
WRITE
CAP_T
R
%
CAPA_T
R
%
CAPB_T
R
%
P1_MAINT
R/W
HR_PUMP1
R
hr
P1_CDOWN
R
hr
P2_MAINT
R/W
HR_PUMP2
R
hr
P2_CDOWN
R
hr
PMP_DLTA
R/W
hr
MODE_24
R
SI_PUMPS
R/W
hr
MODE_5
R
STAGE
R
ROT_PUMP
R/W
TMP_SCTA
R
°F
TMP_SCTB
R
°F
TMP_SSTA
R
°F
TMP_SSTB
R
°F
MODE_9
R
SPT
R/W
°F
MODE_20
R
ST_MAINT
R/W
ST_CDOWN
R
hr
SI_STRNR
R/W
hr
SP_A
R
psig
SP_B
R
psig
SH_A
R
°^F
SH_B
R
°^F
R
R
MODE_14
R
MODE_6
R
R/W
sq m
R/W
sq m
R/W
sq m
R/W
sq m
R/W
sq m
R/W
sq m
R/W
sq m
R/W
sq m
R/W
sq m
R/W
sq m
VHP_ACT
R
mA
MODE_2
R
DEFAULT
RANGE
VALUE
No
Yes/No
No
Yes/No
500
10 - 2000
8760
0 - 65535
No
No/Yes
8760
-40.0 - 245
No
Yes/No
8760
0 - 65535
109
BACNET
BACNET
OBJECT ID
OBJECT NAME
AV:3
cap_t_1
AV:11
capa_t_1
AV:21
capb_t_1
BV:52
p1_maint_1
AV:71
hr_pump1_1
AV:46
p1_cdown_1
BV:53
p2_maint_1
AV:72
hr_pump2_1
AV:47
p2_cdown_1
AV:39
pmp_dlta_1
BV:50
mode_24_1
AV:48
si_pumps_1
BV:33
mode_5_1
AV:9
stage_1
BV:12
rot_pump_1
AV:16
tmp_scta_1
AV:25
tmp_sctb_1
AV:17
tmp_ssta_1
AV:26
tmp_sstb_1
BV:37
mode_9_1
AV:35
spt_1
BV:46
mode_20_1
BV:55
st_maint_1
AV:52
st_cdown_1
AV:51
si_strnr_1
AV:14
sp_a_1
AV:24
sp_b_1
AV:44
sh_a_1
AV:45
sh_b_1
AV:9006
cool_demand_level_1
BV:57
dem_lmt_act_1
BV:40
mode_14_1
BV:34
mode_6_1
AV:2901
user_analog_1_1
AV:2902
user_analog_2_1
AV:2903
user_analog_3_1
AV:2904
user_analog_4_1
AV:2905
user_analog_5_1
BV:2911
user_binary_1_1
BV:2912
user_binary_2_1
BV:2913
user_binary_3_1
BV:2914
user_binary_4_1
BV:2915
user_binary_5_1
AV:19
vhp_act_1
BV:31
mode_2_1