Table 10 — Configuration Mode and Sub-Mode Directory (cont)
KEYPAD
SUB-MODE
ENTRY
OPT2
ENTER
CCN
ENTER
HP.A
ENTER
HP.B
ENTER
ITEM
DISPLAY
CTRL
X
LOAD
X
LLCS
X
XX.X F
LCWT
DELY
XX
ICE.M
ENBL/DSBL
LS.MD
X
LS.ST
00:00
LS.ND
00:00
LS.LT
XXX %
CCNA
XXX
CCNB
XXX
BAUD
X
A1.DT
XX
A2.DT
XX
B1.DT
XX
B2.DT
XX
13
ITEM
EXPANSION
UNIT OPTIONS 2 CONTROLS
CONTROL METHOD
LOADING SEQUENCE SELECT
LEAD/LAG CIRCUIT SELECT
HIGH LCW ALERT LIMIT
MINUTES OFF TIME
ICE MODE ENABLE
LOW SOUND MODE SELECT
LOW SOUND START TIME
LOW SOUND END TIME
LOW SOUND CAPACITY LIMIT
CCN NETWORK CONFIGURATION
CCN ADDRESS
CCN BUS NUMBER
CCN BAUD RATE
HEAD PRESSURE CMP DELTA
SCT DELTA FOR COMP A1
SCT DELTA FOR COMP A2
HEAD PRESSURE CMP DELTA
SCT DELTA FOR COMP B1
SCT DELTA FOR COMP B2
COMMENT
Default: Switch
0 = Enable/Off/Remote Switch
2 = Occupancy
3 = CCN Control
Default: Equal
1 = Equal
2 = Staged
Default: Automatic
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
Default: 60
Range: 2 to 60 F
Default: 0 Minutes
Range: 0 to 15 Minutes
Default: Disable
Default: 0
0 = Mode Disable
1 = Fan Noise Only
2 = Fan/Compressor Noise
Default: 00:00
Default: 00:00
Default: 100%
Range: 0 to 100%
Default: 1
Range: 1 to 239
Default: 0
Range: 0 to 239
Default: 9600
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
Range: 0 - 50 Default: 12
Range: 0 - 50 Default: 12
Range: 0 - 50 Default: 12
Range: 0 - 50 Default: 12