DOK-SUPPL*-VDP*08.3***-PR02-EN-P
Rexroth IndraControl VDP 08.3/40.3 Operator Terminal
Control cabinet PC and display to
Only control cabinet PC connected
to UPS
UPS
(4)
24 V
A
(4)
O V
A
6 mm ² (blue)
(1)
FE = functional earth
10 mm ² (green/yellow)
B
6 mm ²
6 mm ²
6 mm ²
10 mm ² (green/yellow)
A = Terminal block 4 mm²
B = Terminal block 10 mm²
Fig.5-20:
PC (VSB 40.3, VSP xx.3, VPB 40.3, VPP xx.3) and display (VDP xx.3)
connected to an UPS
(4)
24 V
A
(4)
O V
6 mm ² (blue)
A
(1)
B
10 mm ² (green/yellow)
6 mm ²
6 mm ²
6 mm ²
10 mm ² (green/yellow)
A = terminal block 4 mm²
B = terminal block 10 mm²
Fig.5-21:
PC (VSB 40.3, VSP xx.3, VPB 40.3, VPP xx.3) connected to an UPS.
Display (VDP xx.3) not connected to an UPS
Dimensions, Installation and Wiring
Overvoltage category I
Terminal block UK6-FSI/6
with automatic cut-out TCP 10 A
(PHOENIX CONTACT) is recommended
UPS
16 A
(VAU 01.1 )
24V OUT
24V IN
X1S1
X1S2
0V IN
0V OUT
Terminal block UK6-FSI/6
FE
with automatic cut-out TCP 4 A
(PHOENIX CONTACT)
(5)
to be connected to FE of VDP xx.3 .
to be connected to FE of VPB 40.3 , VPP xx.3 , VSB 40.3 , VSP xx.3 .
to be connected to FE of the UPS (VAU 01.1 ).
(1)
Easily removable and visible
(2)
Cable length between UPS and VPB 40.3 and VPP xx.3 max. 2 m at a minimum
cross-section of 2.5 mm ².
(3)
Polarity reversal of the X1S1 and X10 connectors can destroy the device,
if there is no additional external protection (fire danger). This is caused by the
simultaneous grounding of the 0 V of the device and the 0 V (PELV) (1).
(4)
Cable length between +24 V power supply unit and UPS max. 2 m at a minimum
cross-section of 5 mm ² (see project planning manual of the UPS VAU 01.1).
(5)
Cable length between +24 V power supply unit and VDP xx.3 max. 30 m at a minimum
cross-section of 1.5 mm ². An additional power supply unit is required if the length exceeds 30 m.
Overvoltage category I
Terminal block UK6-FSI/6
with automatic cut-out TCP 10 A
(PHOENIX CONTACT) is recommended
UPS
16 A
(VAU 01.1 )
24V OUT
24V IN
X1S1
X1S2
0V IN
0V OUT
FE
Terminal block UK6-FSI/6
with automatic cut-out TCP 4 A
(PHOENIX CONTACT) is recommended
FE = functional earth
(5)
a
to be connected to FE of VDP xx.3 .
a
to be connected to FE of VPB 40.3 , VPP xx.3 , VSB 40.3 , VSP xx.3 .
a
to be connected to FE of the UPS (VAU 01.1 ).
(1)
Easily removable and visible.
Cable length between UPS and VPB 40.3 and VPP xx.3 max. 2 m at a minimum
(2)
cross-section of 2.5 mm ².
(3)
Polarity reversal of the X1S1 and X10 connectors can destroy the device,
if there is no additional external protection (fire danger). This is caused by the
simultaneous grounding of the device and the 0 V (PELV) (1).
(4)
Cable length between +24 V power supply unit and UPS max. 2 m at a minimum
cross-section of 5 mm ² (see project planning manual of the UPS VAU01.1).
(5)
Cable length between +24 V power supply unit and VDP xx.3 max. 30 m at a minimum
cross-section of 1.5 mm ². An additional power supply unit is required if the length exceeds 30 m.
Bosch Rexroth AG
39/81
VSB 40.3
VSP xx.3
VPB 40.3
VPP xx.3
(2)
+
(3)
X10
-
VDP xx.3
+
(3)
X1S1
-
VSB 40.3
VSP xx.3
VPB 40.3
VPP xx.3
(2)
+
(3)
X10
-
VDP xx.3
+
(3)
X1S1
-
FE
FE
FE
FE