Hot-Swapping IC693/IC694BEM331 Modules

Genius Bus Controller modules IC693/694BEM331 that are included in a Max-ON
redundancy system should not be removed from or installed in the PLC that is operating as
a Master. If a module is removed from the Master and then reinstalled, the outputs for that
module will not be enabled until the next Backup-to-Master transition.
Note:
System Consideration
Any time a Genius bus controller is removed or installed in an active system, there is a
possibility that the bus may be disrupted with a subsequent impact on the corresponding I/O
devices. For systems that require online maintainability, it is recommended that dual
(redundant) Genius busses be used