Output Overcurrent Detection - Daikin FTXM-V Series Service Manual

Table of Contents

Advertisement

SiUS042113E

4.27 Output Overcurrent Detection

L5
Error Code
Method of Error
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Detection
Error Decision
 A position signal error occurs while the compressor is running.
Conditions
 A rotation speed error occurs while the compressor is running.
 An output overcurrent signal is fed from the output overcurrent detection circuit to the
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 11 minutes without any other error
Supposed
 Poor installation condition
Causes
 Closed stop valve
 Defective power module
 Wrong internal wiring
 Abnormal power supply voltage
 Defective outdoor unit PCB
 Power supply voltage out of specification
 Defective compressor
Part 6 Service Diagnosis