Omron SYSMAC 3G8F7-CLK12-E Operation Manual page 118

Controller link support boards for pci bus
Table of Contents

Advertisement

Response Codes
Main code
22: Not executable in
current mode
d
23: No Unit
24: Start/stop not
possible
102
Sub-
Probable cause
code
01
The mode is wrong (executing).
Data links are active.
02
The mode is wrong (inactive).
Data links are active.
03
The PC is in the PROGRAM mode.
04
The PC is in the DEBUG mode.
05
The PC is in the MONITOR mode.
06
The PC is in the RUN mode.
07
The specified node is not the control
node.
08
The mode is wrong and the step
cannot be executed.
01
A file device does not exist where
specified.
02
The specified memory does not exist.
03
No clock exists.
01
The data link tables either have not
been created or are incorrect.
Section
Remedy
Check the operating mode.
Check the data link status before
execution.
Check the operating mode.
Check the data link status before
execution.
Check the PC's mode and the computer
mode.
Check the PC's mode and the computer
mode.
Check the PC's mode and the computer
mode.
Check the PC's mode and the computer
mode.
Check which node is the control node.
Check whether the step has active status
or not.
Mount the Memory Card or disk
Check the specifications of the installed file
memory.
Check the model number.
Set the data link tables correctly.
6-4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac 3g8f7-clk52-eSysmac 3g8f7-clk21-e

Table of Contents