Echoback Test; Broadcast Test Results Read - Omron SYSMAC 3G8F7-CLK12-E Operation Manual

Controller link support boards for pci bus
Table of Contents

Advertisement

Commands and Responses for the Support Board
Response Block
Description

6-3-11 ECHOBACK TEST

Command Block
Response Block
Parameters

6-3-12 BROADCAST TEST RESULTS READ

Command Block
94
06
06
Command
Response
code
code
None of the disconnection information except for the Disconnected Line Flags is
cleared when communications recover. The Disconnected Line Flags always
show the most current disconnection status. Disconnected Node Information 1
and 2 are overwritten whenever new information is generated. This command,
however, can be used to clear the disconnection information to its default status.
When the command is executed, the disconnection information and the ring sta-
tus is cleared from the Controller Link Unit/Board and the starting time for dis-
connection information is reset. (The time will be taken from the clock data in the
local node.)
Disconnection information is cleared only from the node that receives this com-
mand. The command must be sent to all nodes in the network to clear all of the
disconnection information.
Disconnection information can also be cleared from the Controller Link Support
Software (Ver. 2.00 or higher), and can be cleared for all nodes at the same time
(in one operation).
Executes an echoback communications test between specified nodes.
1,998 bytes
08
01
max.
Command
Test data
code
1,998 bytes
08
01
max.
Command
Response
code
code
Test data (command, response): For the command, up to 1,998 bytes of data
can be specified to be sent to a specified node. For the response, the test data
that was sent by the command is returned unchanged.
An error is generated if the data returned by the response is different from the
data that was sent by the command.
Reads for each node the results (number of receptions) of a BROADCAST
TEST DATA SEND command that has been sent to all nodes in a specified net-
work. (For details on the BROADCAST TEST RESULTS SEND command, refer
to 6-3-13 BROADCAST TEST DATA SEND.
08
02
Command
code
Test data
Section
6-3