Omron SYSMAC 3G8F7-CLK12-E Operation Manual page 108

Controller link support boards for pci bus
Table of Contents

Advertisement

Commands and Responses for the Support Board
Command Block
Response Block
06
05
Command
Response
code
code
Parameters
92
06
05
Command
code
Disconnected
Disconnected
Line Flags
node in-
formation 1
4 bytes
4 bytes
No. of network
No. of network
separations
disconnections
4 bytes
4 bytes
No. of frame
No. of broken
dropouts for SL2
frames for SL1
Disconnected Line Flags (response): The line disconnection status is re-
turned as follows:
1st byte
15 14 13 12 11 10 9
0
0 0 0 0
Network Disconnected Flag
0: Normal
1: Disconnected
Disconnected node information 1 and 2 (response): The address of the dis-
connected node and the direction of the disconnection from the node (upstream
or downstream) are returned.
Disconnection Direction Flag
0: SL1 (upstream)/Normal
1: SL2 (downstream)
Disconnected node information is returned for two disconnections:
Node Information 1 and Disconnected Node Information 2.
Starting time for disconnection information storage (response):These pa-
rameters show the seconds, minutes, hour (0 to 23), date, month, and year (the
rightmost two digits) in BCD specifying the last time the local node was turned
ON, the Controller Link Unit/Board was reset, or the disconnection information
was cleared. The time will be taken from the clock data in the local node.
Number of network separations (response): Specifies the number of times
the local node has been separated from the network since the starting time for
disconnection information. The value is given as an 8-digit hexadecimal value.
Disconnected
Min
Sec
node in-
formation 2
4 bytes
4 bytes
No. of local node
Max. No. of cycles
with continuous
disconnections
disconnections
4 bytes
4 bytes
No. of broken
No. of CRC
frames for SL2
errors for SL1
2nd byte
8
7
6
5
4
3
2
0 0
0 0 0 0
Local Node Disconnection Direction Flag
0: SL1 (upstream)
1: SL2 (downstream)
Local Node Disconnected Flag
0: Normal
1: Disconnected
1st byte
15 14 13 12 11 10 9
8
7
0 0
0 0 0 0 0
Disconnected Node Address
(2-digit hexadecimal (00: No
disconnection information))
Section
Date Hours Year
Month
4 bytes
No. of frame
dropouts for SL1
4 bytes
No. of CRC
errors for SL2
1
0
0 0
2nd byte
6
5
4
3
2
1
0
Disconnected
6-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac 3g8f7-clk52-eSysmac 3g8f7-clk21-e

Table of Contents