Mounting and Wiring VMA1400 Series Controllers Technical Bulletin
Figure 13: VMA LED Indicator Location
Table 12: LED Indications
If LED is...
Interpretation
On solid
LED is running a 20 second power up self test. Allow it to
continue.
Blinking once per
LED has passed diagnostics, but no N2 messages have
second
been received for this VMA address. Check N2 address
and definition in supervisory controller.
Irregularly flashing
The supervisory system is polling the VMA.
about four times
N2 communication is established.
every second
Rapid flashing
Needs code download. Using HVAC PRO software, click
about 20 times per
Download<VMA Code.
second
Note:
Not lit
The VMA is not receiving power, or +15 V has shorted.
Note:
For any unusual conditions, such as fast regular blinking or no LED
indication, refer to the Troubleshooting Variable Air Volume Module
Assembly (VMA) 1400 Series Controllers Technical Bulletin
(LIT-6363135).
LED
HVAC PRO software must be attached directly to
the N2 Bus of the controller to perform a code
download. You cannot download code from the
Metasys system or over the Zone Bus.