Mounting and Wiring VMA1400 Series Controllers Technical Bulletin
Table 10: Terminations for Single Duct Supply/Exhaust
Cooling with Reheat Applications (VMA1420 and VMA1430)
Name
Description
AI-1*
Zone temperature
AI-2*
Zone setpoint
AI-3
Exhaust air velocity pressure
AI-4
Supply air temperature or sideloop
AO-1 and AO-2
Box or supplemental proportional heat or proportional
damper actuators
BI-1*
Temporary occupied and LED
BI-2
Comfort (occupied)
BI-3
Window, off (shutdown)
BO-1, BO-2, BO-3,
Box heat, supplemental heat, electric heat, lights, humidity,
BO-4, and BO-5
actuator for exhaust damper
Zone Bus*
User interface bus (commissioning, testing, balancing)
* Connected through an 8-pin phone cable from the room sensor.
Table 11: Terminations for Dual Duct Applications
(VMA1420 or VMA1430)*
Name
Description
AI-1
Zone temperature
AI-2
Zone setpoint
AI-3
Hot deck velocity pressure
AI-4
Discharge air temperature or sideloop
AO-1 and AO-2
Supplemental heat or proportional damper actuators
BI-1
Temporary occupied and LED
BI-2
Comfort (occupied)
BI-3
Window, off (shutdown)
BO-1, BO-2, BO-3,
Floating/3-wire damper actuators, supplemental heat, lights
BO-4, and BO-5
* VMA1420 or VMA1430 must be used on Cold Air deck.
Note:
AI-5 (velocity pressure) and the damper actuator are not
listed in any of the above tables because they are internal
points that do not require wiring.