6.9

Checking flue integrity

Flue integrity check
▶ The combustion casing must be fitted whilst this test is carried out.
▶ Refit the test point plugs after the test has been completed.
The integrity of the flue system and performance of the appliance can be
checked via the flue turret/adaptor sample points.
Air inlet sample point location on flue turret/adaptor.
1
Fig. 66 Flue integrity check test point
[1]
Air inlet sample point
[2]
Flue turret air inlet blank plug (with retaining ring)
[3]
Flue adaptor air inlet blank plug
▶ With the appliance combustion casing on and the appliance running
at maximum output in chimney sweep mode
( chapter 6.4 "Chimney sweep mode"), remove the blanking plug
[2 or 3] for the air inlet sample point [1].
▶ Insert the analyser probe into the air inlet sample point [1].
▶ Allow the readings to stabilise and check that:
– O
is equal to, or greater than 20.6%
2
– CO
is less than 0.2%
2
▶ If the readings are outside these limits then this indicates that there
is a problem with the flue system or combustion circuit.
6.10

Flue gas analysis

NOTICE
Combustion testing
▶ Combustion testing must be carried out by a competent qualified
person. Testing must not be attempted unless the person carrying
out the combustion check is equipped with a calibrated Flue Gas
Analyser conforming to BS 7967 and is competent in its use.
Flue gas analysis
▶ Ensure that the gas inlet pressure has been checked and is
satisfactory.
▶ Refit the test point plugs after the test has been completed.
The flue gas analysis performance of the appliance can be checked via
the flue turret/adaptor sample points.
Refer to figure 67 for the location of the flue gas sample point on flue
turret/adaptor.
Greenstar 4000 – 6 720 891 161 (2020/09)
2
3
0010015568-001
1
Fig. 67 Combustion test
[1]
Flue gas sample point
[2]
Flue turret flue gas blank plug
[3]
Flue adaptor flue gas blank plug
The CO and combustion ratio are checked;
• In chimney sweep mode at maximum output.
• In chimney sweep mode at minimum output.
Appliance to maximum output
▶ Set the appliance running at maximum output in chimney sweep
mode ( chapter 6.4 "Chimney sweep mode").
Appliance to minimum output
▶ Set the appliance running at minimum output in chimney sweep
mode ( chapter 6.4 "Chimney sweep mode").
– Allow the appliance to stabilise at minimum output.
Measuring the CO and combustion ratio.
▶ Remove the blanking plug [2 or 3] for the flue gas sample point [1].
▶ Insert the analyser probe into the flue gas sample point [1].
– Ensure that the probe reaches the centre of the flue gas exhaust,
adjust the cone on the probe so that it seals the sample point and
correctly positions the end of the probe.
▶ Check the CO and combustion readings.
When running in maximum output in test mode, and the water
temperature is 74°C or less, the appliance will operate both the central
heating and DHW circuits with the internal diverter valve in the mid
position. It will be necessary to run sufficient water through the DHW
circuit to ensure that the appliance will not cycle on low heating
demands. This is to allow sufficient time for the setting procedure. When
the water temperature reaches 75°C the diverter valve will switch to CH
only and will only return to the mid position if the temperature is 65°C or
less.