Primary system considerations - Combi & System appliances
Sealed system
• The CH sealed system must be filled using a WRAS approved filling
loop or comply with examples in section 4.1.4 "System fill".
• Where the system volume is more than 100 litres or exceeds 2.5 bar
at maximum heating temperature an additional expansion vessel [2]
must be fitted as close as possible to the appliance in the central
heating return.
• Pressurise the extra expansion vessel [2] to the same value as the
built-in expansion vessel [1] (default pre-charge pressure is 0.75
bar).
1
2
3
Fig. 4
Additional expansion vessel
[1]
Appliance expansion vessel
[2]
Additional expansion vessel
[3]
Pressure relief discharge
[4]
Heating return
[5]
Heating flow
Checking the size of the expansion vessel
To determine whether an additional expansion vessel is required: Follow
the steps below:
▶ Calculate the total system volume (litres).
– Plot a line vertically on the chart ( Fig. 5).
▶ Determine the central heating maximum operating flow temperature.
– Plot a line horizontally on the chart ( Fig. 5).
▶ Determine the pre-charge in the expansion vessel based on static
head, 1 metre = 0.1 bar.
– Static head should be measured between the expansion vessel
and the highest point on the system (top of the highest radiator).
▶ Select a curve from the key below (1-5).
▶ System pressure should be set at 0.1 - 0.25 bar higher than the
vessel pre-charge.
– It must be at least to the minimum on appliances with an analogue
gauge.
– Minimum pressure settings may need to be adjusted to suit on,
appliances with a digital gauge, in the applicable menu function.
– Intelligent filling settings may need to be adjusted to suit on,
appliances with the automatic filling accessory, in the applicable
menu function.
If the dissected lines are in area A then no additional expansion is
required.
If the dissected line is in are B then an additional expansion vessel must
be installed ( Fig. 4).
Greenstar 4000 – 6 720 891 161 (2020/09)
Fig. 5
1
4
2
3
4
5
5
A
0010021117-001
B
T
V
The default pre-charge pressure for the expansion vessel is 0.75 bar
4.1.3
Sealed primary system - Single central heating circuit:
Typical primary system example
Fig. 6
[1]
T[°C]
90
80
70
5
60
50
A
40
30
0
100
200
300
Curves for the expansion vessel
Pre-charge pressure 0.5 bar (minimum)
Pre-charge pressure 0.75 bar
Pre-charge pressure 1.0 bar
Pre-charge pressure 1.2 bar
Pre-charge pressure 1.3 bar
Operational capacity of the expansion vessel (left of the relevant
curve)
Additional expansion vessel required (right of the relevant curve)
Maximum operating temperature [ °C]
Total System Volume [l]

System layouts examples

1
Single central heating circuit example
Appliance
Pre-Installation
B
4
3
2
1
400
500
600
700
V[l]
0010036810-001
13