Backing Up Configurations To The Pc; Applying Configurations To The Panel - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

10.7 Backing up configurations to the PC

10.8 Applying configurations to the panel

A6V10421795_en--_k
NOTICE
After firmware update completion, open the backed-up configuration file in
FC360 Panel Configurator, check whether the original settings remain
unchanged, apply the configuration file to the panel and then perform
maintenance test including function and device tests. See chapters 'Applying
configurations to the panel [➙ 117]' and 'Maintenance [➙ 120]' for more
details.
Backed-up event logs cannot be restored to the panel. Keep them in the PC
for necessary check/use in future.
Firmware update doesn't change alarm counter and display style on the LCD.
See chapter 'Appendix F: Flash file behaviors [➙ 140]' for more details.
After the panel firmware is updated, the firmware of output card (4M) (if installed)
and the detection module are also updated automatically.
To update the firmware of FT2010/FT2011/FDUL221, see
document A6V10210416 mentioned in chapter 'Applicable documents [➙ 9]'.
1. Connect the PC to the panel. See 'Connecting a PC to the panel' for panel
connection.
2. Open a web browser.
3. Enter 'fc360.siemens.com' in the address bar and press <enter>.
 'FC360 Panel Configurator' is open.
4. Enter access level 3 password to log into access level 3 on the panel.
5. Click 'Backup', and then click 'OK' to confirm the backup.
6. Select a backup option.
7. If prompted, enter a path and a file name, and then click 'OK'.
 A configuration backup is stored to the PC.
8. Log out of 'FC360 Panel Configurator' and disconnect the PC from the panel.
NOTICE
Before configuring the system manually, make sure that the panel is in normal
operation.
1. Connect the PC to the panel. See 'Connecting a PC to the panel' for panel
connection.
2. Open a web browser.
3. Enter 'fc360.siemens.com' in the address bar and press <enter>.
 'FC360 Panel Configurator' is open.
4. Enter access level 3 password to log into access level 3 on the panel.
Commissioning
Backing up configurations to the PC
10
117 | 151

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc362 seriesFc361-zzFc361-zaFc362-zzFc362-za

Table of Contents