Siemens FC361 Series Technical Manual page 101

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

9.4.8.1 Manual line calibration
9.4.8.2 Calibration report
A6V10421795_en--_k
The line calibration also shows the maximum possible current consumption of all
line devices per line card.
Time of a line calibration process
The duration of a line calibration consists of a 45-second base time plus about 1
second per installed 'Voice alarm sounder beacon/Voice al. sound. beacon base'
device on the line to be calibrated. This means a line with 252 'Voice alarm
sounder beacon/Voice al. sound. beacon base' devices can be calibrated in about
10 minutes.
Calibration mode
Calibration of the selected line can only be triggered manually on the ↑ PMI.
Calibrate all lines manually on the ↑ PMI in the following cases:
The line topology has been changed.
The configuration of the brightness level and/or the sound level of the alarm
devices has changed.
The PMI displays a calibration error for a line.
Calibrating lines manually
The panel blocks the execution of line calibration if there are faults on either
↑ detector line(s) or addressable devices on the line(s). The panel blocks line
calibration too if the system is in alarm condition.
 The fire control panel has started up.
 There are no alarms or faults present on the fire control panel.
 Required access level: 3
1. Press
on the keypad.
 The 'Main menu' window is open.
2. Select 'Engineering' and press
 The 'Engineering' window is open.
3. Select 'Detector line' and press
 The 'Detector line' window is open.
4. Select 'Calibration' and press
 The 'Calibration' window is open.
5. Select 'Calibrate' and press
 A confirmation window is displayed.
6. Press
to confirm.
 The system calibrates lines and then stores the calibration report for the lines.
The calibration report contains the main measurement results or the calibration
figures for all lines calculated from these results.
Displaying the calibration report on the ↑ PMI
 Required access level: 3
.
.
.
.
Engineering
9
Detector line
101 | 151

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc362 seriesFc361-zzFc361-zaFc362-zzFc362-za

Table of Contents