9.4.6.4 Locating a single device
9.4.6.5 Quitting locating devices
A6V10421795_en--_k
4. Select 'Locate' and press
 The 'Locate' window is open.
5. Select 'Lines' and press
 A list of all detector lines is displayed.
6. Select one line and press
 Two commands are listed: 'Locate' and 'Quit locate'.
7. Select 'Locate' and press
 A confirmation window is displayed.
8. Press
to confirm.
 All the devices in the selected line are located.
 The LED indicators on the devices are flashing.
This function is used to find a single device (element) on site.
1. Press
on the keypad.
 The 'Main menu' window is open.
2. Select 'Engineering' and press
 The 'Engineering' window is open.
3. Select 'Detector line' and press
 The 'Detector line' window is open.
4. Select 'Locate' and press
 The 'Locate' window is open.
5. Select 'Element' and press
 A list of all single devices is displayed.
6. Select one desired element and press
 Two commands are listed: 'Locate' and 'Quit locate'.
7. Select 'Locate' and press
 A confirmation window is displayed.
8. Press
to confirm.
 'ON' is displayed on the screen, indicating that the element is now being
located.
 The LED indicator on the element is flashing.
1. Press
on the keypad.
 The 'Main menu' window is open.
2. Select 'Engineering' and press
 The 'Engineering' window is open.
3. Select 'Detector line' and press
 The 'Detector line' window is open.
4. Select 'Locate' and press
 The 'Locate' window is open.
5. Select 'Zones', 'Element', 'Devices' or 'Lines' and then press
 A list of all subparts is displayed.
6. Select one desired subpart and press
 Two commands are listed: 'Locate' and 'Quit locate'.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Engineering
9
Detector line
.
99 | 151