7 Function overview
7.1 Access levels
A6V10421795_en--_k
The panel is protected against unauthorized operation by access levels.
The authorization passwords for access level 2, access level 3 and access
level 3.1 can be changed either directly on panel or with 'FC360 Panel
Configurator'.
Acces
Personnel
s level
1
Anybody
2
Authorized user 1234 or
3
Commissioning
engineer
3.1
4
1
This function is available directly under Main menu for access level 1 if
checkbox 'Lamp test activation possible at access level 1' is checked under
task card 'Other settings' in 'FC360 Panel Configurator'.
Password
Function
(Default)
●
No
View pending events.
Operate the system, e.g.
key switch
●
Acknowledge, operate and reset
or input
events.
●
Disable/enable ↑ zone, device, alarm
devices, ↑ RT alarm, and RT fault.
●
Perform detection test, lamp test
voice test
●
View event log and compensation
value log.
●
Automatic logout after a period of no
operation.
●
Access code is not necessary if a key
switch is used.
●
Access code is not necessary if the
input configured as 'access level 2' is
activated.
●
9999
Configure system.
●
Automatic logout after a period of no
operation.
●
Restart a ↑ detector line.
9999
●
66666666
Reset alarm counter.
Function overview
7
Access levels
1
and
59 | 151