7 Function overview

7.1 Access levels

A6V10421795_en--_k
The panel is protected against unauthorized operation by access levels.
The authorization passwords for access level 2, access level 3 and access
level 3.1 can be changed either directly on panel or with 'FC360 Panel
Configurator'.
Acces
Personnel
s level
1
Anybody
2
Authorized user 1234 or
3
Commissioning
engineer
3.1
4
1
This function is available directly under Main menu for access level 1 if
checkbox 'Lamp test activation possible at access level 1' is checked under
task card 'Other settings' in 'FC360 Panel Configurator'.
Password
Function
(Default)
No
View pending events.
Operate the system, e.g.
key switch
Acknowledge, operate and reset
or input
events.
Disable/enable ↑ zone, device, alarm
devices, ↑ RT alarm, and RT fault.
Perform detection test, lamp test
voice test
View event log and compensation
value log.
Automatic logout after a period of no
operation.
Access code is not necessary if a key
switch is used.
Access code is not necessary if the
input configured as 'access level 2' is
activated.
9999
Configure system.
Automatic logout after a period of no
operation.
Restart a ↑ detector line.
9999
66666666
Reset alarm counter.