6.11.4 Output card (4M) (FCA3602-Z1)

A6V10421795_en--_k
FCA3602-Z1
Fig. 19: Installation of output card (4M)
Fig. 20: Connection overview of output card (4M)
Fig. 21: Connection of internal power
Function:
The output card (4M) has four monitored outputs: OUT1...OUT4.
The default settings for the outputs are:
OUT1: RT Fire
OUT2:RT Fault
OUT3/OUT4: Sounder line
DC 24 V @ 2 A power supply is required. There are two options for power
connection:
Internal connection. See Fig. 'Connection of internal power'.
External connection. Power is provided via external power supply (FP120-Z1).
For connection terminals on the output card (4M), see Fig. 'Connection
overview of output card (4M)'.
NOTICE! Output card (4M) doesn't support multiple transmission paths in
one cable!
In addition to the default monitoring (short and open), the outputs can be
configured to monitor the output lines for creeping open and creeping short circuits.