8.5.3 Viewing event memories

8.5.3.1 Viewing event logs
A6V10421795_en--_k
All events that happened in the fire detection system are stored in event logs. You
can view them one by one on the panel or view them all in a PC after uploading.
See 'Backing up event logs to the PC [➙ 118]' for more information about viewing
event logs in a PC.
There are 8 event categories:
Alarm
Fault
Technical
Isolation
Test
Activation
Information
Operation
The event lists are sorted chronologically and can be filtered by category and time.
When you view event logs, the displayed view is almost the same as 'Event views
[➙ 66]'. Device IDs in event logs are only visible for access level 3 or above, as is
the case with device IDs in event views. In addition, the symbols '+', '-', 'c' are
displayed in front of the event type to indicate the processing status of the event:
1. '+': event in
2. '-': event out
3. 'c': operation on ↑ PMI
To view all events
1. Press
on the keypad. The 'Main menu' window is open.
Main menu
1 - System status
2 - Operation
3 - Event memory
4 - Login
5 - Lamp test
7 - Logout
2. Select 'Event memory' and press
Event memory
1 - Event log
3 - Compensation Value
3. Select 'Event log' and press
Operations under access level 2
L2
. The 'Event memory' window is open.
L2
. The 'Event log' window is open.
Operation
8
81 | 151