 Input Method
Set the connection method of input analog signal.
With the CPSN-AI-2408LI, only Differential Input is available when one of the switches is set to
"Current Input".
CPSN-AI-2408LI
[Setting]: Single-ended Input, Differential Input
[Default]: Single-ended Input
 Input Range
Set the range of voltage (current) that can input.
CPSN-AI-2408LI
[Setting]: Voltage Input: ±10V, ±5V, ±2.5V, 0 - 10V, 0 - 5V
Current Input: ±20mA, 0 - 20mA
[Default]: ±10V
 Channels to use
Select the channel number to be used.
CPSN-AI-2408LI
[Setting]: CH0 - CH7
[Default]: Use all
CPSN-SSI-4C
[Setting]: CH0 - CH3
[Default]: Use all
 Input Data Range
Set the valid range of input data.
Values outside the range are rounded down to the minimum value or rounded up to the maximum
value. If a value outside the range is detected, the LED of corresponding channel flashes.
CPSN-AI-2408LI
[Setting]: The minimum value to the maximum value set in the input range (settable up to the first
decimal place).
[Default]: -10.0 - +10.0
 Power Supply Noise (50/60Hz) Rejection
Set this to "Enabled" to reject the noises caused by the commercial frequencies (50/60Hz).
CPSN-AI-2408LI
[Setting]: Disabled, Enabled
[Default]: Enabled