Input Method
Set the connection method of input analog signal.
With the CPSN-AI-2408LI, only Differential Input is available when one of the switches is set to
"Current Input".
CPSN-AI-2408LI
[Setting]: Single-ended Input, Differential Input
[Default]: Single-ended Input
Input Range
Set the range of voltage (current) that can input.
CPSN-AI-2408LI
[Setting]: Voltage Input: ±10V, ±5V, ±2.5V, 0 - 10V, 0 - 5V
Current Input: ±20mA, 0 - 20mA
[Default]: ±10V
Channels to use
Select the channel number to be used.
CPSN-AI-2408LI
[Setting]: CH0 - CH7
[Default]: Use all
CPSN-SSI-4C
[Setting]: CH0 - CH3
[Default]: Use all
Input Data Range
Set the valid range of input data.
Values outside the range are rounded down to the minimum value or rounded up to the maximum
value. If a value outside the range is detected, the LED of corresponding channel flashes.
CPSN-AI-2408LI
[Setting]: The minimum value to the maximum value set in the input range (settable up to the first
decimal place).
[Default]: -10.0 - +10.0
Power Supply Noise (50/60Hz) Rejection
Set this to "Enabled" to reject the noises caused by the commercial frequencies (50/60Hz).
CPSN-AI-2408LI
[Setting]: Disabled, Enabled
[Default]: Enabled
—
CONPROSYS nano WEB Setting
CPSN-PCB271-S1-041 Reference Manual (Software)
— 29 —
—