Firefighters Mode - Honeywell BC-200 Operation, Installation & Programming Manual

Table of Contents

Advertisement

Panel Operation
7.2 F
IREFIGHTERS
Only the one screen is available in this mode. The "soft" buttons control the functions available.
This mode is automatically entered when any unacknowledged alarm is present, and until all alarms are
acknowledged or cleared, no other screen can be selected. The top right corner of the screen shows a quick
system status, giving the total alarms, faults, isolates and non-alarm events at that time.
The soft button functions for this screen operate as follows:
PREV
Will scroll the cursor up the list to the previous item.
NEXT
Will scroll the cursor down the list to the next item.
ACKN
Will cause the alarm to be marked as acknowledged.
Will perform a point reset function on the currently highlighted alarm. As per AS4428,
you will be requested to press ACKN to confirm the reset. Any other button will abort
RESET
the reset. The point is automatically acknowledged by this action. Once an alarm is
reset, it will be removed from the screen, however if the alarm condition is still present,
it will re-alarm after a 15 second time out.
Will perform a point isolate function on the currently highlighted alarm. As per AS4428,
you will be requested to press ACKN to confirm the isolate. Any other button will abort
the isolate. The point is automatically acknowledged by this action. Once an alarm is
ISOL
isolated, it will be remain on the screen marked as an isolated alarm and must be reset
to clear from the alarm screen. Once an alarm is isolated, to deisolate the alarm you
must go through the service menu, isol/deisol function.
Note:
If "group zones" for FireFighters display is selected for AS4428, the zone displayed in fire fighters mode may
be a collection of several points on the system. Resetting or isolating a zone will result in all the underlying
points being isolated or reset. To view, isolate or reset individual alarm points you must go to the Service
Menu and list alarms, after acknowledging all active alarms.
BC-200 Manual – P/N DOC-01-013
M
ODE
NOTIFIER INERTIA AFP2800 FIP
DAY MODE
20 JULY 2002 14:44:37
ZONE
LABEL
PENTHOUSE
ZONE 23
STAIRWELL
ZONE 22
PREV
NEXT
ACKN
A = 2
F = 0
I = 0
N = 0
STATUS
TIME
20 July 10:12
ALARM
1/2
20 July 10:07
ACKD ALARM
2/2
RESET
ISOL
24