Panel Operation
System points will be displayed and can be referred to as follows:
Description
On Board AZF's
AZF #1
AZF #2
On Board Relays
Relay 1 to 8 on FIM
Distributed Field Modules
AZF
Din
Dout
Description
Annunciator
Inputs
Outputs
Analog Addressable Devices
Detectors
Modules
Virtual Points
Network Points
Expansion Relays
System Parameters
Common Alarm
Common Fault
Common Isolate
Battery Fault
Charger Fault
Mains On
Ext. Bell Isolated
Warning System Isolated
BC-200 Manual – P/N DOC-01-013
Syntax
Comments
2 AZF's on termination Board
0.1.Z1
Ring 0 Module 1, zone 1
0.1.Z2
Ring 0 Module 1, zone 2
8 Relays on termination Board
0.4.O1 to 0.4.O8
Ring 0 Module 4, output 1
Ring 0 Module 4, output 8
Up to 100 modules
1.1.Z1
8 AZF points per AZM8module
1.1.I1
3 Din Per Fan Control Module
1.1.O1
4 Dout Per AZM-8
3 Dout Per Fan Control Module
Syntax
Comments
Up to 50 Annunciators
1.101.I1
16 Din per 16AT, 24 Din Per SCS-8
1.101.O1
32 Dout Per 16AT, 24 Dout Per SCS-8, 32
Dout Per ACM32A
Up to 4 Loops
L1D1
99 Detectors Per Loop
L1M1
99 Modules Per Loop
VPn
n can range up to 1000
NPn
n can range up to 1000
XRn
n can range up to 64
CA
CF
CI
BF
CL
MO
BI
WI
22