Detector Type
Beam
Default
Thermal
Default
9.5.3.1
SMAERT 4
Smart 4 is a CLIP only Multi-Criteria detector that is programmed as an "Acclimate" detector to allow backward
compatibility with older versions of software. Six different sensitivity settings are available with this detector.
The sensitivity settings and suggested applications for each setting are listed in the following table.
Sensitivity
Suggested Application
Level 1
Ultra clean environments -
Laboratories
Level 2, 3
Clean environments – Offices
Level 4
Moderately clean environments –
Hotel/Dorm rooms
Level 5, 6
Moderate environments – hotel near
shower, boiler rooms
Level 7, 8
Harsh environments – Equipment
Default
rooms, kitchens, night clubs
Level 9
Harsh environments
Notes: - The delay counter starts when the smoke level exceeds approximately 2.46% per metre. Maximum of 10
minutes delay from processed photo output. If there is a detection of another fire signature (Carbon
Monoxide, Infrared or Thermal) the detector overrides the 10 minute confirmation time.
- Use of AVF function is not permitted by AS1670.1 at sensitivity levels 5, 6, 7, 8 and 9.
- Smart 4 is a CLIP only detector and should be programmed as an "Acclimate".
- Level 9 may be used with day/night settings to provide heat only detection during certain times of the day.
BC-200 Manual – P/N DOC-01-013
Analog Addressable Detectors Sensitivity Settings Table
Total Obscuration
Level 1
Level 2
Level 3
Level 4
Level 5
30 - 40% Auto
Level 6
40 - 50% Auto
Level 7
Level 8
Level 9
Degrees Celsius
Level 1
Level 2
Level 3
Level 4
Level 5
Level 6
S
ENSITIVITY AND
Alarm
25%
30%
40%
50%
-
-
-
O
43
C
O
57
C
O
63
C
O
68
C
O
74
C
O
90
C
A
PPLICATION
Details
3.28% per metre of smoke or greater than 45 ppm of CO.
No delays from processed photo output
6.56% per metre of smoke. No delays from processed
photo output
9.84% per metre of smoke. No delays from processed
photo output
9.84% per metre of smoke. Maximum of 10 minutes delay
from processed photo output. See notes.
13.12% per metre of smoke. Maximum of 10 minutes
delay from processed photo output. See notes.
Heat only alarm. If the heat level on either thermistor
exceeds 63°C or rate of rise limits.
Pre-Alarm
Total Obscuration
50%
55%
60%
65%
70%
75%
80%
85%
90%
Degrees Celsius
O
40
C
O
43
C
O
57
C
O
65
C
O
70
C
O
75
C
G
UIDE
106