Honeywell BC-200 Operation, Installation & Programming Manual page 29

Table of Contents

Advertisement

Panel Operation
7.3.3.1
S
ERVICE
This screen will display all individual alarm conditions active at the time. As new alarms (unacknowledged) force
the panel into Fire Fighters mode, this page can only be accessed once all alarms are acknowledged.
INDIVIDUAL POINT ALARM LIST
DAY MODE
20 JULY 2002 14:44:37
TIME
TYPE
20 JULY 14:01
SMOKE
L1D1
PENTHOUSE
20 JULY 14:40
HEAT
1.10.Z1
NORTH STAIRWELL
PREV
NEXT
7.3.3.2
S
ERVICE
This list will display all system faults in chronological order. If faults are set as non-latching, they will self clear
from this list. If faults are set to latching, a reset action from this list is the only way to clear them. Once a fault is
isolated it remains in the fault list but does not operate the fault outputs. Faults on Analog points will also indicate
a fault code as shown in the example screen below (refer to section 9.5).
FAULT LIST
DAY MODE
20 JULY 2002 14:44:37
TIME
TYPE
20 JULY 10:00
SMOKE
L1D1
PENTHOUSE
20 JULY 12:15
HEAT
1.10.Z1
STAIRWELL
PREV
NEXT
Note:
You can also use the arrow keys, the Page Up and Page Dn keys on an external keyboard for scrolling
functions.
BC-200 Manual – P/N DOC-01-013
M
– L
ENU
IST
A = 2
F = 0
I = 0
N = 0
STATUS
NUMBER
ACKD ALARM
1 OF 2
ACKD ALARM
2 OF 2
ACKN
RESET
ISOL
M
– L
ENU
IST
A = 0
F = 2
I = 1
N = 0
STATUS
NUMBER
FAULT (F01)
1 OF 2
ISOL FAULT
2 OF 2
ACKN
RESET
ISOL
– A
LARM
Actions:
Use the PREV and NEXT buttons to scroll
through the active Alarms.
Use ACKN to acknowledge currently highlighted
alarm.
Use RESET to reset the currently highlighted
alarm.
You will be asked to press ACKN to confirm, press
any other button to abort.
Use ISOL to isolate the currently selected alarm.
You will be asked to press ACKN to confirm, press
any other button to abort.
– F
AULT
Actions:
Use the PREV and NEXT buttons to scroll
through the faults.
Use ACKN to acknowledge currently selected
fault.
Use RESET to reset the currently selected fault.
You will be asked to press ACKN to confirm, press
any other button to abort.
Use ISOL to isolate the currently selected fault.
You will be asked to press ACKN to confirm, press
any other button to abort.
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents