5.4 OPER DATA - REMOTE PRINTOUT

The following shows a typical example YCRS printout
obtained by pressing the 'OPER DATA' key with an
optional printer attached.
YORK INTERNATIONAL CORPORATION
MILLENNIUM SCREW CHILLER
UNIT STATUS
2:04PM 10 OCT 99
SYS 1
NO COOLING LOAD
SYS 2
COMPRESSOR RUNNING
OPTIONS
CHILLED LIQUID
AMBIENT CONTROL
REFRIGERANT TYPE
PROGRAM VALUES
DSCH PRESS CUTOUT
DSCH PRESS UNLOAD
SUCT PRESS CUTOUT
HIGH AMBIENT CUTOUT
LOW AMBIENT CUTOUT
LEAVING LIQUID CUTOUT
MOTOR CURRENT UNLOAD
ANTI RECYCLE TIME
LOCAL/REMOTE MODE
LEAD/LAG CONTROL
UNIT DATA
LEAVING LIQUID TEMP
RETURN LIQUID TEMP
MIXED LIQUID TEMP
COOLING RANGE
AMBIENT AIR TEMP
LEAD SYSTEM
EVAPORATOR PUMP
EVAPORATOR HEATER
ACTIVE REMOTE CONTROL
SOFTWARE VERSION
54
WATER
STANDARD
R-22
399 PSIG
375 PSIG
44 PSIG
130.0 DEGF
25.0 DEGF
36.0 DEGF
100 %FLA
600 SECS
REMOTE
AUTOMATIC
49.0 DEGF
58.2 DEGF
51.3 DEGF
42.0 + / - 2.0 DEGF
74.8 DEGF
SYS 2
ON
OFF
NONE
C.ACS.09.00
FORM 201.25-NM1 (302)
SYSTEM 1 DATA
COMPRESSORS STATUS
RUN TIME
0- 0-00-00 D-H-M-S
MOTOR CURRENT
0
AMPS 00 %FLA
SUCTION PRESSURE
125 PSIG
DISCHARGE PRESSURE
131 PSIG
OIL PRESSURE
SUCTION TEMPERATURE
DISCHARGE TEMPERATURE
71.8 DEGF
OIL TEMPERATURE
3.4 DEGF
SAT SUCTION TEMP
74.5 DEGF
SUCTION SUPERHEAT
6.3 DEGF
SAT DISCHARGE TEMP
74.5 DEGF
DISCHARGE SUPERHEAT
6.3 DEGF
SLIDE VALVE STEP
0
COOLER INLET REFRIG
44.6 DEGF
LIQUID LINE SOLENOID
OIL COOLING SOLENOID
COMPRESSOR HEATER
WYE-DELTA RELAY
SYSTEM 2 DATA
COMPRESSORS STATUS
RUN TIME
0- 0-15-26 D-H-M-S
MOTOR CURRENT
104 AMPS 87 %FLA
SUCTION PRESSURE
57 PSIG
DISCHARGE PRESSURE
233 PSIG
OIL PRESSURE
SUCTION TEMPERATURE
DISCHARGE TEMPERATURE
145.5 DEGF
OIL TEMPERATURE
102.8 DEGF
SAT SUCTION TEMP
31.7 DEGF
SUCTION SUPERHEAT
11.2 DEGF
SAT DISCHARGE TEMP
112.1 DEGF
DISCHARGE SUPERHEAT
33.4 DEGF
SLIDE VALVE STEP
70
COOLER INLET REFRIG
23.6 DEGF
LIQUID LINE SOLENOID
OIL COOLING SOLENOID
COMPRESSOR HEATER
WYE-DELTA RELAY
DAILY SCHEDULE
S M T W T F S *=HOLIDAY
MON START=00:00AM STOP=00:00AM
TUE START=00:00AM STOP=00:00AM
WED START=00:00AM STOP=00:00AM
THU START=00:00AM STOP=00:00AM
FRI START=00:00AM STOP=00:00AM
SAT START=00:00AM STOP=00:00AM
HOL START=00:00AM STOP=00:00AM
YORK INTERNATIONAL
OFF
130 PSIG
68.4 DEGF
OFF
OFF
OFF
OFF
ON
218 PSIG
42.9 DEGF
ON
ON
ON
OFF