York YCRS Series Installation, Operation And Maintenance Manual page 56

Water cooled remote condenser 81 tons through 194 tons (285 kw through 682 kw)
Table of Contents

Advertisement

Micropanel
S U C T I O N
P R E S S U R E
C U T O U T
=
4 4
H I G H
A M B I E N T
C U T O U T
=
1 3 0 . 0
L O W
A M B I E N T
C U T O U T
=
2 5 . 0 ° F
L E A V I N G
L I Q U I D
C U T O U T
=
3 6 . 0 ° F
H I G H
M O T O R
U N L O A D
-
1 0 0 %
L O C A L / R E M O T E
L O C A L
L E A D / L A G
C O N T R O L
A U T O M A T I C
L C H L T
=
4 4 . 1
R C H L T
=
5 2 . 9
This message indicates the leaving and return chilled
liquid temperatures at the time of the fault.
L H L T
=
4 6 . 4
This message indicates the leaving hot liquid tempera-
ture at the time of the fault on units with water cooled
condensers.
S E T P O I N T
R A N G E
=
+ /
This message displays the programmed chilled liquid
setpoint and deviation (control range) programmed at
the time of the fault.
A M B I E N T
=
7 7 . 6 ° F
This message indicates the outdoor ambient air tem-
perature at the time of the fault.
L E A D
S Y S T E M
S Y S T E M
N U M B E R
56
P S I G
T E M P
° F
T E M P
T E M P
C U R R E N T
F L A
M O D E
° F
° F
° F
=
4 4 . 0 ° F
2 . 0 ° F
A I R
T E M P
I S
1
This message indicates which refrigerant system was
in the lead at the time of the fault.
E V A P
P U M P
This message indicates the status of the evaporator
pump signal from the microprocessor.
A C T I V E
R E M O T E
N O N E
This message indicates that a remote device such as a
Remote Control Center, an ISN controller, or another
device sending a PWM signal for temperature or cur-
rent reset is overriding control points programmed
through the keypad or default microprocessor setpoints.
System Data:
Following the common data is a sequence of system
messages, which are repeated for each refrigerant sys-
tem. These messages display system parameters at the
time of the fault:
• Compressor status (ON or OFF)
• System run time since the last compressor start
(in Days, Hours, Minutes, and Seconds)
• Compressor motor current
(as a percentage of FLA)
• System differential oil pressure, suction pressure
and discharge pressure
• System oil temperature, suction temperature and
discharge temperature
• Compressor suction gas saturation temperature and
superheat
• Compressor discharge gas saturation temperature
and superheat
• Compressor slide valve position (Step 0 = mini-
mum capacity, Step 75 = fully loaded)
• Refrigerant temperature at the inlet of the cooler
Liquid line solenoid valve and oil cooling solenoid
valve, when fitted, position (ON = e n e r g i z e d ,
OFF = de-energized)
• Stage of condenser fan operation (remote air cooled
condenser if fitted) and status of the compressor
heater
• Wye-Delta timer output.
FORM 201.25-NM1 (302)