Electrical Connection; Power Wiring; Units With Single-Point Power Supply Wiring; Units With Multi-Point Power Supply Wiring - York YCRS Series Installation, Operation And Maintenance Manual

Water cooled remote condenser 81 tons through 194 tons (285 kw through 682 kw)
Table of Contents

Advertisement

Installation

ELECTRICAL CONNECTION

The following connection recommendations are intended
to ensure safe and satisfactory operation of the unit.
Failure to follow these recommendations could cause
harm to persons, or damage to the unit, and may invali-
date the warranty.
No additional controls (relays, etc.)
should be mounted in the control
panel. Power and control wiring not
connected to the control panel should
not be run through the control panel.
If these precautions are not followed
it could lead to a risk of electrocution.
In addition, electrical noise could
cause malfunctions or damage the
unit and its controls.
After connection do not switch on
mains power to the unit until it has
been commissioned by YORK Autho-
rized personnel. Some internal com-
ponents are live when mains is
switched on.
The unit ON/OFF rocker switch on the front of the
control panel has been set in the "OFF" position at the
factory.
This switch MUST remain in the "OFF" position until
the unit is commissioned by YORK Authorized person-
nel. If the switch is set to the "ON" position before
commissioning then it must be reported to YORK, oth-
erwise the warranty may be invalidated.

POWER WIRING

All electrical wiring should be carried out in accordance
with local regulations. Route properly sized cables to
cable entries on the bottom of the control panel. For
wiring specifications, refer to Section 9.
In accordance with National Electrical Code (N.E.C.)
it is the responsibility of the user to install overcurrent
protection devices between the supply conductors and
the power supply terminals on the unit.
24
To ensure that no eddy currents are set up in the metal
gland plate the cables forming each 3-phase power sup-
ply must enter via the same hole in the gland plate. If
separate entries for each cable forming the 3-phase
supplies are used, the metal gland plate must be re-
placed by a non-metallic gland plate, with due regard
given to sealing the panel to NEMA 1.
All sources of supply to the unit must
be taken via a common points of iso-
lation (not supplied by YORK).

Units with Single-Point Power Supply Wiring

Models require one field provided 200, 3Ø, 60 Hz;
230VAC, 3Ø, 60 Hz; 380V, 3Ø, 60 Hz; 460V, 3Ø, 60
Hz; 575V, 3Ø, 60 Hz, ground supply to the unit with
circuit protection.
Connect the 3-phase supply to the terminal block or
non-fused disconnect switch located in the common
input section using the wire sizes detailed in Section 9.
Connect the earth wire ground to the main protective
earth terminal in the common input section.

Units with Multi-Point Power Supply Wiring

Units require two field provided 200, 3Ø, 60 Hz; 230VAC,
3Ø, 60 Hz; 380V, 3Ø, 60 Hz; 460V, 3Ø, 60 Hz; 575V,
3Ø, 60 Hz, supplies with circuit protection and a separate
control supply with circuit protection (200, 3Ø, 60 Hz;
230VAC, 3Ø, 60 Hz; 380V, 3Ø, 60 Hz; 460V, 3Ø, 60
Hz; 575V, 3Ø, 60 Hz, + ground).
Connect each of the 3-phase supplies to the door inter-
locked circuit breakers located in the power sections,
using the wire sizes detailed in Section 9.
Connect each of the earth grounds to the main protec-
tive earth ground terminals in the power sections.
Connect the control supply to the door interlocked emer-
gency stop device located in the common input section,
using the wire sizes detailed in Section 9.
Connect the earth ground to the main protective earth
terminal in the common input section.
FORM 201.25-NM1 (302)