Local Printer Option - York YCRS Series Installation, Operation And Maintenance Manual

Water cooled remote condenser 81 tons through 194 tons (285 kw through 682 kw)
Table of Contents

Advertisement

5.8 LOCAL PRINTER OPTION

The Micro Panel is capable of supplying a printout of
chiller conditions or fault shutdown information at any
given time. This allows operator and service personnel
to obtain data and system status with the touch of the
keypad. In addition to manual print selection, the mi-
cro panel will provide an automatic printout whenever
a fault occurs. An explanation of the keypad use to ob-
tain a printout is discussed in the "PRINT" KEY Sec-
tion on Page 52.
YORK recommends the field tested WEIGH-TRONIX
IMP-24, Model 2600 printer. This is a compact low cost
printer that is ideal for service work and data logging.
Paper is in the form of a compact roll and is easily
handled compared to larger printers using wider busi-
ness form style paper. The paper is 2.25" wide desktop
calculator paper that can be easily and inexpensively
purchased at most stationery stores. Shown in Fig. 17
and 18 is the WEIGH-TRONIX printer and a typical
sample printout.
The WEIGH-TRONIX IMP-24 Model 2600 printer can
be purchased for approximately $150.00. Contact
Weigh-Tronix for purchase information:
Weigh-Tronix
2320 Airport Blvd.
Santa Rosa, Ca. 95402
Phone: 1-800-358-9110 or 1-707-527-5555
(International Orders Only)
The printout is made to be universal
to all types of chillers both air and wa-
ter cooled with or without options.
Items may be indicated on the print-
out which may not be present on the
chiller.
Installation Limitations
The following limitations must be adhered to. Failure
to do so may result in improper printer and/or chiller
operation.
1. The printer option is adaptable to all versions and
revisions of Microprocessor boards and EPROMs.
No modifications are necessary to the panel.
2. Maximum cable length between the printer and the
Microprocessor Board is 25 feet. Twisted pair
shielded cable is required.
3. The printer must be supplied a 115VAC source.
4. The printer may be left connected to the micro panel.
YORK INTERNATIONAL
FIG. 17 – WEIGH-TRONIX IMP-24 MODEL 2600
PRINTER
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SYSTEM STATUS
8:45AM 6/3/98
SYS 1
COMPRESSOR RUNNING
SYS 2
ANTI-COIN TIMER 13 SEC
RETURN WATER TEMP
LEAVING WATER TEMP
LOW WATER CUTOUT
SETPOINT TEMP
OUTSIDE AIR TEMP
LOW AMBIENT CUTOUT
LOW PRESSURE CUTOUT
LEAD SYSTEM
CONTROL TYPE
COOLING RANGE
SYSTEM 1 DATA
COMPRESSOR STATUS
MOTOR AMPS
SUCTION PRESSURE
DISCHARGE PRESSURE
OIL PRESSURE
LIQUID LINE SOLENOID
RUN PERMISSIVE
STAGES OF LOADING
FORWARD FANS
REVERSE FANS
HOT GAS BYPASS VALVE
SYSTEM 2 DATA
COMPRESSOR STATUS
MOTOR AMPS
SUCTION PRESSURE
DISCHARGE PRESSURE
OIL PRESSURE
LIQUID LINE SOLENOID
RUN PERMISSIVE
STAGES OF LOADING
FORWARD FANS
REVERSE FANS
HOT GAS BYPASS VALVE
S M T W T F S
SUN
START=06:00AM
MON
START=06:00AM
TUE
START=06:00AM
WED
START=06:00AM
THU
START=06:00AM
FRI
START=06:00AM
SAT
START=06:00AM
HOL
START=00:00AM
FIG. 18 – PRINTOUT
FORM 201.25-NM1 (302)
23899A
65.0 DEGF
54.0 DEGF
36.0 DEGF
45.0 DEGF
75.0 DEGF
10.0 DEGF
4 4 PSIG
SYS 1
LCHWT
45.0 TO 47.0 DEGF
ON
50 %FLA
61 PSIG
143 PSIG
75 PSID
OFF
ON
1
OFF
OFF
OFF
ON
0 %FLA
61 PSIG
80 PSIG
1 PSID
OFF
ON
1
1
OFF
OFF
=HOLIDAY
STOP=11:00PM
STOP=11:00PM
STOP=11:00PM
STOP=11:00PM
STOP=11:00PM
STOP=11:00PM
STOP=11:00PM
STOP=00:00AM
59
7

Advertisement

Table of Contents
loading