Remote Run/Stop; Remote Print (Pnt); Remote Setpoint Offset - Temperature; Remote Setpoint Offset - Current - York YCRS Series Installation, Operation And Maintenance Manual

Water cooled remote condenser 81 tons through 194 tons (285 kw through 682 kw)
Table of Contents

Advertisement

Installation

Remote Run/Stop

Connect remote switch(es) in series with the flow switch
to provide remote run/stop control if required.

Remote Print (PNT)

Closure of suitable contacts connected to terminals 28
and 13 will enable a hard copy printout of Operating
Data/Fault History to be obtained (an optional printer
must be connected to the RS 232 port on the micropro-
cessor board).
26
Remote Setpoint Offset – Temperature (PWMT)
Timed closure of suitable contacts connected to termi-
nals 27 and 13 (PWM contacts) will give remote offset
function of the chilled liquid setpoint if required.
Remote Setpoint Offset – Current (PWMC)
Timed contact closure of a suitable contact connected
to terminals 26 and 13 (PWM contact) will give re-
mote offset of EMS% CURRENT LOAD LIMIT.