Endress+Hauser Gammapilot M FMG60 FOUNDATION Fieldbus Operating Instructions Manual

Endress+Hauser Gammapilot M FMG60 FOUNDATION Fieldbus Operating Instructions Manual

Radiometric measurement
Table of Contents

Advertisement

Quick Links

BA00330F/00/EN/16.18
71401076
2018-08-13
Products
Operating Instructions
Gammapilot M FMG60
FOUNDATION Fieldbus
Radiometric measurement
Solutions
Services

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Gammapilot M FMG60 FOUNDATION Fieldbus

  • Page 1 Products Solutions Services BA00330F/00/EN/16.18 71401076 2018-08-13 Operating Instructions Gammapilot M FMG60 FOUNDATION Fieldbus Radiometric measurement...
  • Page 2 Gammapilot M FMG60 FOUNDATION Fieldbus Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
  • Page 3 Gammapilot M FMG60 FOUNDATION Fieldbus Gammapilot M - Quick guide Gammapilot M - Quick guide A0036818-EN Endress+Hauser...
  • Page 4 Contents of these Operating Instructions Gammapilot M FMG60 FOUNDATION Fieldbus Contents of these Operating Instructions These Operating Instructions describe how to install and commission the radiometric compact transmitter Gammapilot M. All of the functions that are necessary for standard measuring tasks are included. In addition, the Gammapilot M provides many additional functions for optimizing the measuring point and for converting the measured value.
  • Page 5: Table Of Contents

    Gammapilot M FMG60 FOUNDATION Fieldbus Table of contents Table of contents 4.2.4 Installation conditions for density About this document ....7 and concentration measurements . . . 19 Document function .
  • Page 6 Disposal ......Contact addresses at Endress+Hauser ..82 Accessories .
  • Page 7: About This Document

    Gammapilot M FMG60 FOUNDATION Fieldbus About this document About this document Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
  • Page 8: Symbols For Certain Types Of Information

    About this document Gammapilot M FMG60 FOUNDATION Fieldbus 1.2.4 Symbols for certain types of information Symbol Meaning Permitted Procedures, processes or actions that are permitted. Preferred Procedures, processes or actions that are preferred. Forbidden Procedures, processes or actions that are forbidden.
  • Page 9: Basic Safety Instructions

    Gammapilot M FMG60 FOUNDATION Fieldbus Basic safety instructions Basic safety instructions Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
  • Page 10: Radiation Protection

    Basic safety instructions Gammapilot M FMG60 FOUNDATION Fieldbus WARNING ‣ The three screws connecting the detector pipe to the terminal housing may not be opened. A0018068 WARNING ‣ Depending on the certificate ordered, observe the associated safety instructions →  94...
  • Page 11: Workplace Safety

    Gammapilot M FMG60 FOUNDATION Fieldbus Basic safety instructions Source container Document FQG60 TI00445F/00/EN FQG61, FQG62 TI00435F/00/EN FQG63 TI00446F/00/EN QG2000 TI00346F/00/EN BA00223F/00/EN Time The time spent in the exposed area should be kept to a minimum. Distance Keep as far away from the radiation source as possible. The radiation intensity decreases in proportion to the square of the distance from the radiation source.
  • Page 12 Gammapilot M FMG60 FOUNDATION Fieldbus It meets general safety standards and legal requirements. It also complies with the EC directives listed in the device-specific EC Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device. Endress+Hauser...
  • Page 13: Product Description

    Gammapilot M FMG60 FOUNDATION Fieldbus Product description Product description Product design 3.1.1 Components of the FMG60 A0018069  1 A: Gammapilot M without water cooling jacket; B: Gammapilot M with water cooling jacket; C: Gammapilot M with collimator Terminal housing...
  • Page 14: Nameplates

    Information on the required temperature resistance of the connecting cables (only for device versions with a water cooling jacket) Scope of delivery • Ordered version of the device (including Operating Instructions) • Endress+Hauser operating program (on the CD-ROM supplied) • Accessories as ordered Endress+Hauser...
  • Page 15: Accompanying Documentation

    The device takes into account the applicable standards and regulations which are listed in the EC Declaration of Conformity and thus meets the legal requirements of the EC directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 16: Installation

    Installation Gammapilot M FMG60 FOUNDATION Fieldbus Installation Incoming acceptance, product identification, transport, storage 4.1.1 Incoming acceptance Check the packaging and contents for any signs of damage. Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
  • Page 17: Installation Conditions For Level Measurement

    Gammapilot M FMG60 FOUNDATION Fieldbus Installation Gammapilot M with water cooling jacket or collimator 537 (21.14) 12 (0.47) 164 (6.46) mm (in) A0018073 Type Measuring Without water cooling jacket With water cooling jacket length A [mm Total length Weight [kg...
  • Page 18: Installation Conditions For Point Level Detection

    Installation Gammapilot M FMG60 FOUNDATION Fieldbus Examples A0018074 Vertical cylinder; the Gammapilot M is mounted vertically with the detector head pointing downwards, the gamma ray is aligned to the measuring range. Cascading of multiple Gammapilot M devices; there is no gap between the measuring ranges...
  • Page 19: Installation Conditions For Density And Concentration Measurements

    • If only horizontal pipes are accessible, the path of the beam should also be arranged horizontally to minimize the influence of air bubbles and deposits. • The Endress+Hauser clamping device FHG61 or an equivalent clamping device should be used to fasten the radiation source container and the Gammapilot M to the measuring tube.
  • Page 20 Installation Gammapilot M FMG60 FOUNDATION Fieldbus A0018076 Vertical beam (90°) Diagonal beam (30°) Measurement section Sample point • To increase the accuracy of density measurements, the use of a collimator is recommended. The collimator screens the detector against environmental radiation.
  • Page 21: Empty Pipe Detection

    Installation conditions for flow measurement Measurement of solids flow In conjunction with a density meter, such as Endress+Hauser' s "Gammapilot M", Promag 55S also determines the rate of solids in terms of mass, volume or percentage. The following order information is required for this purpose for Promag 55S: Order option for the "Solids flow"...
  • Page 22: Water Cooling

    Installation Gammapilot M FMG60 FOUNDATION Fieldbus Measurement of mass flow Bulk solids applications on conveyor belts and conveyor screws. The source container is positioned above the conveyor belt and the Gammapilot M FMG60 below the conveyor belt. The radiation is attenuated by the medium on the conveyor belt.
  • Page 23: Mounting Position And Position Of The Cooling Water Nozzles

    Gammapilot M FMG60 FOUNDATION Fieldbus Installation A0023205 Cylinder screws CAUTION Consider the following when using the water cooling jacket ‣ It is recommended to ground the water cooling jacket separately at the protective ground connection provided for this purpose. ‣...
  • Page 24: Required Flow

    Installation Gammapilot M FMG60 FOUNDATION Fieldbus CAUTION ‣ The water must always be introduced from the bottom to ensure that the water cooling jacket is completely filled. 4.3.2 Required flow The required flow rate depends on: • The ambient temperature at the water cooling jacket •...
  • Page 25 Gammapilot M FMG60 FOUNDATION Fieldbus Installation • Is the device damaged (visual inspection)? • Does the device match the measuring point specifications (ambient temperature, measuring range etc.)? • If available: are the measuring point number and labeling correct (visual inspection)? •...
  • Page 26: Wiring

    Wiring Gammapilot M FMG60 FOUNDATION Fieldbus Wiring Connection compartments The Gammapilot M has two connection compartments A0018082 Connection compartment 1 Connection compartment 2 Connection compartment 1 Connection compartment for: • Power supply • Signal output (depending on the device version)
  • Page 27: Terminal Assignment

    Gammapilot M FMG60 FOUNDATION Fieldbus Wiring • Cable entry NPT1/2 • M12 connector (see "Fieldbus connectors") • 7/8" connector (see "Fieldbus connectors") In addition, the Gammapilot M also has a socket to connect the separate display and operating unit FHX40. The housing of the Gammapilot M does not have to be opened to connect the FHX40.
  • Page 28 Wiring Gammapilot M FMG60 FOUNDATION Fieldbus SIM WP PT100 11 12 IN CASCADE OUT A0018085  5 For the terminal assignment, see the table below Terminal Meaning Grounding of the cable shield 1, 2 Power supply Connection com- Signal output, depending on communication version: partment 2: •...
  • Page 29: Fieldbus Connectors

    Gammapilot M FMG60 FOUNDATION Fieldbus Wiring Connection compartment with terminals for Feature 30 of the ordering information: power supply wiring/output wiring Supply volt- Signal out- Non-Ex; non-Ex Ex e; Ex ia Ex e; Ex e Ex d (XP); Ex d (XP) Ex d (XP);...
  • Page 30: Foundation Fieldbus Terminal Voltage

    Wiring Gammapilot M FMG60 FOUNDATION Fieldbus Hazardous area: • Siemens 6XV1 830-5AH10 (blue) • Belden 3076F • Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL Foundation Fieldbus terminal voltage All of the following voltages are terminal voltages directly at the device: Version Minimum terminal voltage...
  • Page 31: Wiring In Connection Compartment 1

    Gammapilot M FMG60 FOUNDATION Fieldbus Wiring Wiring in connection compartment 1 CAUTION Note the following before connecting: ‣ If the device is used in hazardous areas, make sure to comply with national standards and the specifications in the Safety Instructions (XAs). The specified cable gland must be used.
  • Page 32: Wiring In Connection Compartment 2

    Wiring Gammapilot M FMG60 FOUNDATION Fieldbus Wiring in connection compartment 2 CAUTION Note the following before connecting: ‣ Connect the potential matching line to the external ground terminal of the transmitter and to the ground terminal of the water cooling jacket (if present) before connecting the device.
  • Page 33 Gammapilot M FMG60 FOUNDATION Fieldbus Wiring A0018089 Gammapilot M FMG60 Cable of the display and operating unit FHX40 For some Dust-Ex versions of the Gammapilot M, the FHX40 connector is protected by a metal sleeve: A0018090 1. Loosen the sleeve with an Allen key and remove it 2.
  • Page 34: Wiring For Cascade Mode

    Wiring Gammapilot M FMG60 FOUNDATION Fieldbus 5.11 Wiring for cascade mode N/L- L1/L+ AC/DC A0018091 Power supply (90 to 253VAC or 18 to 35VDC ) Junction box Master Slave End slave There are two options for attaching the circuit breaker as per IEC/EN 61010: •...
  • Page 35: Operation

    • With a personal computer, Commubox FXA291 with ToF Adapter FXA291 (USB) and the "FieldCare" operating program. FieldCare is a graphical operating software for measuring devices from Endress+Hauser. It assists with commissioning, data backup, signal analysis and documentation of the measuring point.
  • Page 36: Display Operation

    Operation Gammapilot M FMG60 FOUNDATION Fieldbus Display operation 6.2.1 Display and operating elements The LCD module VU331 for displaying and operating is located inside the remote display and operating unit FHX40. The measured value can be read through the FHX40 window.
  • Page 37: The Operating Menu

    Gammapilot M FMG60 FOUNDATION Fieldbus Operation Symbol Meaning COM_SYMBOL This communication symbol is displayed when data transmission via HART, PROFIBUS PA or FOUN- DATION Fieldbus, for example, is in progress. SIMULATION_SWITCH_ENABLE This communication symbol is displayed when simulation in FOUNDATION Fieldbus is enabled via the DIP switch.
  • Page 38 Operation Gammapilot M FMG60 FOUNDATION Fieldbus • The alphabetic character indicates the current measurement mode of the Gammapilot – L: Level – S: Switch – D: Density – C: Concentration – *: no measurement mode selected yet • The first numeric character identifies the function group: –...
  • Page 39: Alternative Operation Options

    Operation with FieldCare FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare you can configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT standard. Hardware and software requirements can be found on the Internet: www.de.endress.com ->...
  • Page 40: Locking/Unlocking Configuration

    Operation Gammapilot M FMG60 FOUNDATION Fieldbus FieldCare supports the following functions: • Configuration of transmitters in online mode • Loading and saving device data (upload/download) • Documentation of the measuring point Connection options: Commubox FXA291 with ToF Adapter FXA291 via service interface Locking/unlocking configuration 6.4.1...
  • Page 41: Foundation Fieldbus Interface

    Gammapilot M FMG60 FOUNDATION Fieldbus Operation FOUNDATION Fieldbus interface 6.6.1 System architecture The following diagram shows two typical examples of a FOUNDATION Fieldbus network with the associated components. ENDRESS + HAUSER – A0018251 Fieldcare, Profiboard/Proficard FF link Micropilot M with display VU331...
  • Page 42: Network Configuration

    • When the configuration is finished, close the tool and the FF stack (if open) The device descriptions for the Gammapilot M device descriptions can be ordered directly from Endress+Hauser or downloaded from our website "www.endress.com". They contain all the data needed to operate Endress+Hauser Foundation Fieldbus devices.
  • Page 43: Block Model Of The Gammapilot M

    Gammapilot M FMG60 FOUNDATION Fieldbus Operation The device ID consists of the following parts: Device_ID = 452B481013-XXXXXXXXXXX where: 452B48 ID code for Endress+Hauser 1013 ID code for Gammapilot M XXXXXXXXXXX Device serial number as printed on the nameplate. Right-clicking the name opens up a menu in which the PD_TAG and NODE_ADDRESS can be changed.
  • Page 44: Resource Block

    Operation Gammapilot M FMG60 FOUNDATION Fieldbus Default (as-delivered) block configuration The input and output variables of individual blocks can be interconnected by a network configuration tool (e.g. NI-Fieldbus Configurator). The block model below shows how these connections are set in the default (as-delivered) state.
  • Page 45: Transducer Block

    Gammapilot M FMG60 FOUNDATION Fieldbus Operation Parameter Parameter Description TAG_DESC User description of the intended application of the block MODE_BLK Lists the actual, target, permitted and normal operating modes of the block. • Target: changes the operating mode of the block •...
  • Page 46 Operation Gammapilot M FMG60 FOUNDATION Fieldbus Block administration parameters Parameter Description MODE_BLK See the description under Resource block. The possible operating modes of the Transducer block are: • AUTO: the block is operating as normal • OOS: the block is out of service TAG_DESC User description of the intended application of the block.
  • Page 47 Gammapilot M FMG60 FOUNDATION Fieldbus Operation Parameter Position rel.Index Variable Name Size[bytes] Type Read Write Storage Class Indicator Secondary Value SECONDARY_VALUE DS-65 dynamic Secondary Value Unit SECONDARY_VALUE_UNIT UNSIGNED16 static Third Value THIRD_VALUE DS-65 dynamic Third Value Unit THIRD_VALUE_UNIT UNSIGNED16 static...
  • Page 48 Operation Gammapilot M FMG60 FOUNDATION Fieldbus Parameter Position rel.Index Variable Name Size[bytes] Type Read Write Storage Class Indicator Square coefficient SQUARETEMPCOEFF FLOAT non-vol. Linearization (level) GAMMALINEARISATIONLEVEL 1 ENUM8 non-vol. Lin. table number SENSLINTABLENUMBER UNSIGNED8 dynamic Input level INPUTOUTLEVEL FLOAT dynamic...
  • Page 49: Diagnostic Block

    Gammapilot M FMG60 FOUNDATION Fieldbus Operation 6.6.7 Diagnostic block E+H_GAMMAPILOT_M_XXXXXXXXXXX ..TRANSDUCER_XXXXXX (TB) ..DIAGNOSTIC_XXXXXX (DIAG) ..DISPLAY_XXXXXX (DISP) Operation The Diagnostic block contains the error messages of the device. These parameters can also be read out and edited using the VU331 display module. The Diagnostic block is opened by clicking the "Diagnostic"...
  • Page 50: Analog Input Block

    Operation Gammapilot M FMG60 FOUNDATION Fieldbus ..ANALOG_INPUT_XXXXXX (AI) Operation The Display block contains the parameters for configuring the display module VU331 (in the remote display and operating unit FHX40). These parameters can also be read out and edited using the VU 331 display module. The Display block is opened by clicking the "Display"...
  • Page 51 Gammapilot M FMG60 FOUNDATION Fieldbus Operation DIRECT HI_HI INDIRECT LO_LO INDIRECT SQRT FIELD_VAL PROCESS VALUE (PV) A0018675 Operation The Analog Input block is opened by clicking the "Analog_Input" line. Parameter changes using the tool are made offline. The device can remain in operation during this time.
  • Page 52 Operation Gammapilot M FMG60 FOUNDATION Fieldbus Scaling parameters Parameter Description CHANNEL Selects which value is entered in the Analog Input block • 0 = no channel defined • 1 = primary value: measured level/volume • 2 = secondary value: measured distance.
  • Page 53: Commissioning Checklist

    Gammapilot M FMG60 FOUNDATION Fieldbus Operation Alarm priorities Parameter Description The alarm is suppressed Is recognized by the system but is not reported Is reported to the operator but does not require the operator' s attention Advisory alarms of increasing priority...
  • Page 54: Start Index List

    Operation Gammapilot M FMG60 FOUNDATION Fieldbus 3. Configure the Transducer block, Diagnostic block and Display block  •If necessary, change the block tag (right-click the tree) •Set MODE_BLK_TARGET to Out-of-Service •If necessary, assign a new tag description (TAG_DESC) •Configure the device as described in the "Basic setup" section •Set MODE_BLK_TARGET to AUTO...
  • Page 55: Commissioning

    Gammapilot M FMG60 FOUNDATION Fieldbus Commissioning Commissioning This chapter describes how to commission the Gammapilot M using the display and operating module VU331 (which is located in the remote display and operating unit FHX40). Commissioning via "FieldCare" or "Field Xpert SFX100" is performed in a similar manner.
  • Page 56: Basic Setup

    Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus 7.1.1 Basic setup Step Function Entry or selection Comments See page Present date (*01) Sample value: Set the day with ; confirm with 12.11.04 10:30 the same routine applies for the month, year, hour and minute Beam type (*02) •...
  • Page 57: Calibration For Density And Concentration Measurements

    Gammapilot M FMG60 FOUNDATION Fieldbus Commissioning Step Function Action/comments Background pulse rate (*12) Confirm value with Continue with full and empty calibration/covered and free calibration "Full" or "Covered" calibration For details, see "Full and empty calibration or covered and free calibration"...
  • Page 58 Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus Background calibration For details refer to "Background calibration" Step Function Action/comments Switch off radiation Background calibration (*10) Select "Start" with ; confirm with Avg. pulse rate (*11) Wait until the value is stable, then confirm with Background calibration (*10) Select "Stop/edit"...
  • Page 59: Switching On The Device

    Gammapilot M FMG60 FOUNDATION Fieldbus Commissioning Switching on the device Error messages A165 "Electronics defect" and A635 "Present date not defined" The Gammapilot M contains 2 real-time clocks for decay compensation, which are permanently compared with one another for safety reasons. In order to bridge voltage interruptions, the clocks are buffered with a capacitor.
  • Page 60: Basic Setup

    Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus Basic setup 7.3.1 "Present date" (*01) Local display Present date *01 17.11.04 _____10:30 DD.MM.YY ____ HH:MM This function is used to enter the date and time of the basic setup. Each of these values must be confirmed by pressing after entering the value.
  • Page 61: Measurement Mode" (*05)

    Gammapilot M FMG60 FOUNDATION Fieldbus Commissioning A0018107 Stand alone. Only one Gammapilot M is required for measuring ranges up to 2 m (6.6 ft) For larger measuring ranges, any number of Gammapilot M devices can be interconnected (cascade mode). The devices are defined by software settings as:...
  • Page 62: Density Unit" (*06)

    Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus Further options: • Level measurement (continuous) • Point level detection • Density measurement (with temperature compensation if required) • Concentration measurement (density measurement followed by linearization) The operating mode can only be selected once. After this, the function is automatically locked and can only be unlocked by resetting the Gammapilot M ("Reset"...
  • Page 63: Min. Density" (*07)

    Gammapilot M FMG60 FOUNDATION Fieldbus Commissioning • °Baumé; [1°Baumé = 144.3 (1 - 1/x)] • °API; [1°API = 131.5 (1,076/x - 1)] • °Twaddell; [1°Twaddell = 200 (x-1)] "x" refers to the density in g/cm . The formula indicates how many degrees this density corresponds to.
  • Page 64: Output Damping" (*0B)

    Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus 30° 2.0 x D A0018109  8 Always specify the complete irradiated measuring path L in the "Pipe diameter" (*0A) function. Depending on the installation, this value may be larger than the actual pipe diameter.
  • Page 65: Calibration For Level Measurement And Point Level Detection

    Gammapilot M FMG60 FOUNDATION Fieldbus Commissioning Default value The default value depends on the selected "Measurement mode" (*05): • Level: 6 s • Switch: 6 s • Density: 60 s • Concentration: 60 s Selecting the output damping value The output damping value depends on the process conditions. Increasing the output damping value makes the measured value considerably steadier but also slower.
  • Page 66 Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus Full calibration Full calibration refers to the following situation: • The radiation is switched on • The vessel is filled as much as possible (ideally 100%, at least 60%) within the measuring range. If the vessel cannot be filled to at least 60% during the calibration, the full calibration can alternatively be performed with the radiation switched off.
  • Page 67: Background Calibration

    Gammapilot M (e.g. because the vessel cannot be sufficiently filled or emptied), this calibration point must be entered manually. This means that both the level and the associated pulse rate must be entered directly. Please contact Endress+Hauser Service for any questions regarding the calculation of the pulse rate.
  • Page 68 Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus "Background calibration" (*10) Local display Backgr. cal. *10 Stop/edit Start This function is used to start the background calibration Options: • Stop/edit This option must be selected if: – No background calibration is to be performed but the pulse rate of an existing background calibration is to be displayed instead.
  • Page 69: Full And Empty Calibration Or Covered And Free Calibration

    Gammapilot M FMG60 FOUNDATION Fieldbus Commissioning "Stop/edit" option must be selected to stop the integration. The value is then automatically transmitted to the "Background pulse rate" (*12) function. Background pulse rate • The maximum integration time (= averaging time) is 1000 s. After this time, the value is automatically transmitted to the "Background pulse rate"...
  • Page 70 Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus full calibr. value full calibration avg. [c/s] 0: stop / edit puls rate -1: not target value 1: start calibrated at calibr. point Group next point calibr. point selection 0: no 0: full/covered 1: yes 1: empty/free empty calibr.
  • Page 71 Gammapilot M FMG60 FOUNDATION Fieldbus Commissioning Range of values optimum value minimum value maximum value Value full (*14) 100% 100% Value empty (*17) "Calibration" (*15) Local display Calibration *15 Stop/edit Start This function is used to start automatic entry of the selected calibration point Options: •...
  • Page 72: Additional Settings

    Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus option must be selected to stop the integration. The value is then automatically transmitted to the "Full calibration" (*16) or "Empty calibration" (*18) function. Avg. pulse rate • The maximum integration time (= averaging time) is 1000 s. After this time, the value is automatically transmitted to the "Full calibration"...
  • Page 73: Calibration For Density And Concentration

    Gammapilot M FMG60 FOUNDATION Fieldbus Commissioning Calibration for density and concentration measurements 7.5.1 General principles The calibration points for the measurement are entered in the "Calibration" (*1) function group. Each calibration point consists of a density value and the associated pulse rate.
  • Page 74: Background Calibration

    Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus the Gammapilot M only calculates the reference pulse rate I . In this case, it uses the default value µ = 7.7 mm /g for the absorption coefficient. Multiple-point calibration Multiple-point calibration is recommended particularly for measurements in a large density range or for particularly accurate measurements.
  • Page 75 Gammapilot M FMG60 FOUNDATION Fieldbus Commissioning "Background calibration" (*10) Local display Backgr. cal. *10 Stop/edit Start This function is used to start the background calibration Options: • Stop/edit This option must be selected if: – No background calibration is to be performed but the pulse rate of an existing background calibration is to be displayed instead.
  • Page 76: Calibration Points

    Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus "Background pulse rate" (*12) Local display Backgr. pulse rate *12 186 cps The pulse rate of the background calibration is displayed in this function. Press confirm the value and complete the background calibration. If a background calibration has not yet been performed, "-1"...
  • Page 77 Gammapilot M FMG60 FOUNDATION Fieldbus Commissioning "Calibration point" (*1A) Local display Calibration point *1A ✓ 1 This function is used to select the calibration point which will be entered. Further options: • "1" to "9": calibration points for various densities •...
  • Page 78 Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus "E" A0018118 When the value is sufficiently stable users can quit the function by pressing . After this, the Gammapilot M changes to the "Calibration" (*15) function. Here the "Stop/edit" option must be selected to stop the integration. The value is then automatically transmitted to the "Density adjustment"...
  • Page 79 Gammapilot M FMG60 FOUNDATION Fieldbus Commissioning "Calibration point" (*1D) Local display Calibration point *1D Not used  Used Clear This function is used to specify whether the current calibration point is to be used or not. Options: • Not used The calibration point is not used.
  • Page 80: Linearization (For Concentration Measurements)

    Commissioning Gammapilot M FMG60 FOUNDATION Fieldbus Options: • No Select this option if no more calibration points are to be entered or changed. The Gammapilot M then returns to the group selection and the calibration is completed. • Yes Select this option if another calibration point is to be entered or changed. The Gammapilot M then returns to the "Calibration point"...
  • Page 81: Maintenance And Repair

    Repairs to devices with an Ex-certificate When repairing devices with an Ex-certificate, please also note the following: • Repairs to Ex-certified devices may only be carried out by Endress+Hauser Service in Endress+Hauser workshops. • Comply with the prevailing standards, national Ex-area regulations, Safety Instructions (XA) and certificates.
  • Page 82: Disposal

    Maintenance and repair Gammapilot M FMG60 FOUNDATION Fieldbus To ensure swift, safe and professional device returns, please refer to the return procedures and conditions on the Endress+Hauser website at "www.services.endress.com/return- material". Disposal When disposing, separate and recycle the device components based on the materials.
  • Page 83: Accessories

    Accessories Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field devices with a CDI interface (Endress+Hauser Common Data Interface) and the USB port of a personal computer or laptop. For details, see TI00405C/07/EN For Gammapilot M, you also need the "ToF Adapter FXA291" accessory...
  • Page 84: Remote Display And Operating Unit Fhx40

    Accessories Gammapilot M FMG60 FOUNDATION Fieldbus Remote display and operating unit FHX40 9.4.1 Dimensions 120 (4.72) 88(3.46) 82 (3.23) 118 (4.65) 96 (3.78) max. 80 (3.15) min. 30 (1.18) mm (in) A0018138 Wall mounting (without mounting bracket) Pipe mounting (mounting bracket/plate supplied optionally)
  • Page 85: Technical Data (Cable And Housing)

    Gammapilot M FMG60 FOUNDATION Fieldbus Accessories Marking Measuring point (TAG), see additional specifications Use the cables provided for the corresponding communication version of the device to connect the remote display FHX40. 9.4.3 Technical data (cable and housing) Cable length 20 m (66 ft) (fixed length including attached plugs) Temperature range Temperature class T5: –40 to +75 °C (–40 to +167 °F)
  • Page 86: Mounting Device Fhg60 (For Level And Point Level Measurement)

    Accessories Gammapilot M FMG60 FOUNDATION Fieldbus Mounting device FHG60 (for level and point level measurement) 9.5.1 Dimensions 88 (3.46) 30 (1.18) øD M6x80-A2 M6x20-A2 øC max. 6 Nm 116 (4.57) (4.42 lbf ft) 88 (3.46) 63 (2.48) A0018139 Distance as large as possible Retainers (number and size depending on selected application);...
  • Page 87: Use

    Gammapilot M FMG60 FOUNDATION Fieldbus Accessories 9.5.2 Permitted Preferred A0018141 Level measurement, FMG60 without cooling jacket Level measurement, FMG60 with cooling jacket Point level measurement, FMG60 without cooling jacket Point level measurement, FMG60 with cooling jacket Such horizontal mounting not permitted Retainer for pipe diameter 80 mm (3.15 in)
  • Page 88: Clamping Device For Density Measurement Fhg61

    Accessories Gammapilot M FMG60 FOUNDATION Fieldbus • In the Product Configurator on the Endress+Hauser website: www.endress.com -> Select country -> Instruments -> Select device -> Accessories for FMG60 • From an Endress+Hauser Sales Center: www.endress.com/worldwide Product Configurator - the tool for individual product configuration •...
  • Page 89: Rma42, Process Transmitter With Control Unit

    Gammapilot M FMG60 FOUNDATION Fieldbus Accessories An Essential Version of the Field Data Manager (FDM) software is included for SQL- supported data analysis on the PC. The number of inputs available in the basic device can be individually increased using a maximum of 5 plug-in cards.
  • Page 90: Troubleshooting

    Checksum error Contact Endress+Hauser Service A111 Electronics defect Switch device off/on; If the error persists: contact Endress+Hauser Service or replace the transmitter A113 Electronics defect Switch device off/on; If the error persists: contact Endress+Hauser Service or replace the transmitter A114 Electronics defect Switch device off/on;...
  • Page 91 Code Error description Remedial action A121 Electronics defect Switch device off/on; If the error persists: contact Endress+Hauser Service or replace the transmitter W153 Initializing Wait for the initialization procedure to finish A160 Checksum error Contact Endress+Hauser Service A165 Electronics defect •...
  • Page 92: Possible Calibration Errors

    Troubleshooting Gammapilot M FMG60 FOUNDATION Fieldbus Code Error description Remedial action A636 Calibration date not plausi- Check calibration date and enter it again ("System parameters" (*C) function group, "Calibration date" (*C7) function) A637 Operating mode not Enter operating mode defined ("Basic setup"...
  • Page 93: Software History

    Gammapilot M FMG60 FOUNDATION Fieldbus Troubleshooting 10.3 Software history Date Software Software modification Documentation version as of 06.2005 01.01.00 Original software • BA330F/00/en/06.05, 71000010 • BA00287F/00/en/08.04, 52023818 Since 07.2005 01.01.02 Since 11.2005 01.01.04 Bug fix Concentration mode corrected Density measurement recalibration corrected Since 08.2006 01.01.06...
  • Page 94: Technical Data

    Safety Instructions (XA). Certificates For the allocation of the approval to the device version, see the Product Configurator on the Endress+Hauser website: www.endress.com -> Select country -> Instruments - > Select device -> Product page function: Configure this product General...
  • Page 95 Gammapilot M FMG60 FOUNDATION Fieldbus Technical data Approval number: NEPSI GYJ15.1144 Approval feature Type of protection Power supply wiring/ Output (communi- Safety instructions output wiring, option cation), option 040 XA00536F XA01706F Ex de [ia] IIC T6 XA00536F XA00537F Ex d [ia] IIC T6...
  • Page 96 Technical data Gammapilot M FMG60 FOUNDATION Fieldbus Approval Type of protection Power supply Output (com- Safety instruc- feature 010 wiring/ munication), tions output wir- option 040 ing, option XA00335F XA00304F XA00333F II 2(1) G Ex de [ia Ga] IIC T6 Gb XA00303F II 2(1) D Ex tb [ia Da] IIIC T80°C Db...
  • Page 97 TIIS Ex d [ia] IIC T6 D BA00236F CE mark The measuring system meets the legal requirements of the EC Directives. Endress+Hauser confirms that the device has been successfully tested by applying the CE mark. GOST Approval for GOST available...
  • Page 98: Appendix

    Appendix Gammapilot M FMG60 FOUNDATION Fieldbus Appendix 12.1 Operating menu for level measurements value empty A0036819-EN Endress+Hauser...
  • Page 99 Gammapilot M FMG60 FOUNDATION Fieldbus Appendix A0036820-EN All the device functions are described in detail in the following Operating Instructions: BA00287F/00/EN Endress+Hauser...
  • Page 100: Operating Menu For Level Limit (Point Level)

    Appendix Gammapilot M FMG60 FOUNDATION Fieldbus 12.2 Operating menu for level limit (point level) detection A0036821-EN Endress+Hauser...
  • Page 101 Gammapilot M FMG60 FOUNDATION Fieldbus Appendix A0036822-EN All the device functions are described in detail in the following Operating Instructions: BA00287F/00/EN Endress+Hauser...
  • Page 102: Operating Menu For Density And Concentration Measurements

    Appendix Gammapilot M FMG60 FOUNDATION Fieldbus 12.3 Operating menu for density and concentration measurements A0036823-EN Endress+Hauser...
  • Page 103 Gammapilot M FMG60 FOUNDATION Fieldbus Appendix A0036824-EN All the device functions are described in detail in the following Operating Instructions: BA00287F/00/EN Endress+Hauser...
  • Page 104 *71401076* 71401076 www.addresses.endress.com...