4.5 Remote Emergency Stop Kit

The emergency stop (E-stop) kit allows immediate
shutdown of the generator set from a remote location. If
the
emergency
stop
EMERGENCY STOP lamp lights and the unit shuts
down immediately, bypassing the engine cooldown
cycle. Before attempting to restart the generator set,
reset the emergency stop switch and reset the
generator set by pressing and holding the OFF/RESET
button for 3 seconds.
Two emergency stop kits are available. See Figure 4-14
and the following instructions.
4.5.1
Remote Emergency Stop Kit
This switch uses a glass piece that must be replaced
after activation.
1. To stop the generator set, pull down on the handle,
breaking the glass piece.
2. To reset the emergency stop switch, return the
handle to the original position and replace the glass
piece with a new one.
3. Press and hold the controller's OFF/RESET button
for 3 seconds.
Use the single glass piece located inside the switch for
replacement and order additional glass pieces as
service parts.
Remote Emergency Stop Switch
Figure 4-14 Remote Emergency Stop Switches
80
Section 4 Accessories
switch
is
activated,
Insert lockout/tagout device
through these holes
4.5.2

Lockable Emergency Stop Switch

This switch can be locked in the activated position to
prevent generator set starting. Use a customer provided
locking device inserted into the holes in the shroud to
the
lock the switch until the generator set can be operated
safely.
Operation
Press the red STOP button to shut down the generator
set in an emergency.
Using the emergency stop button bypasses the engine
cooldown cycle, stopping the engine immediately. The
emergency stop LED on the RSA III lights (if equipped)
and the unit shuts down. The generator set cannot be
restarted until the emergency stop switch(es) is/are
reset.
Lockout/Tagout
The emergency stop button can be locked in the STOP
position. Insert a lock through two openings in the
yellow shroud to prevent the stop button from being
pulled out. See Figure 4-14.
normal operation.
A lock is not required in order to keep the switch
activated. The switch button will stay depressed until it
is pulled out by the operator.
Resetting the Emergency Stop Switch
To reset the E- stop switch, remove the locking device
and pull the button out. Reset the controller by pressing
and holding the OFF/Reset button for 3 seconds.
Remove the lock for