Menus 5 And 6; Menu 6.5-Communication - Kohler KD800 Operation

Industrial generator sets, controller: apm802
Hide thumbs Also See for KD800:
Table of Contents

Advertisement

2.12.5 Menus 5 and 6

Except for menu 6.5, communication, menus 5 and 6 are view-only menus that can be seen when logged in as an
operator (1966). The view-only menus are not shown in this document.

2.12.6 Menu 6.5-Communication

Screen 6.5.1- Ethernet
The 6.5.1­Ethernet screen defines the computer addresses for the Ethernet connections for the base module and the
HMI module.
Figure 2-75 Ethernet Screen
The screen is accessible for modification at the operator level, but only for the TCP/IP configuration section.
Group
TCP/IP
Addressing mode *
Settings
DNS server
Fault Finding
Base - Eth3/4 IP address *
Base - Eth3/4 MAC address *
HMI - Eth1 IP address *
HMI - Eth1 MAC address *
HMI - Eth2 IP address
* IP = Internet Protocol; MAC = Media Access Control.
Eth1 = Ethernet port marked 1 at the rear of the HMI module
Eth3/4 = Ethernet ports marked 3 or 4 on the front of the base module
DHCP: the DHCP protocol (Dynamic Host Configuration Protocol) allows an APM system to connect to a network, which dynamically
assigns it an IP address
Figure 2-76 Ethernet Settings
66
Section 2 Operation
Title
Choice of address type for the TCP/IP connection: System, Customer
IP, or DHCP.
IP address of the DNS server. The DNS server is used to make the
connection between an APM802 system and an IP address.
Permanent or temporary identification number for the base module
connected to another base or to a mains.
Unique permanent physical identification number, which is stored in
the base module.
Permanent or temporary identification number for the HMI module
connected to another base or to a mains.
Unique permanent physical identification number, which is stored in
the HMI module.
Not used.
Description and Possible Settings