Saved Electrical And Mechanical Data - Kohler KD800 Operation

Industrial generator sets, controller: apm802
Hide thumbs Also See for KD800:
Table of Contents

Advertisement

2.9.4

Saved Electrical and Mechanical Data

The recording on a USB stick provides a curve data file
(.csv) containing the information shown in Figure 2-25.
Depending on the engine type and sensors installed on
the generator set, some of the 14 mechanical values
may not be used. In that case, 0 will appear in the Excel
table for the value or values concerned.
For electrical values, the voltage input U2 of the
regulation module is present in the Excel table even
though this input is not used.
The markers I3.x.x and I5.x.x correspond to the analog
variable numbers (see section 2.12.4).
Mechanical value
I5.35: U bat #1
I5.36: I bat #1
I5.10: Engine speed
I5.21: Daily tank fuel level
I5.20: Engine cooling circuit coolant level
I5.15: Fuel temperature
I5.16: Oil temperature
I5.13: Engine cooling circuit coolant temperature
I5.14: Charge air cooling circuit coolant temperature
I5.17: Charge air temperature
I5.24: Oil pressure
I5.25: Low fuel pressure
I5.27: Charge air pressure
I5.115: ECU: Estimated instant fuel consumption
I5.131: ECU: Common rail fuel pressure
I5.110: ECU: Engine speed
I5.138: ECU: ECU voltage supply
I5.139: ECU: Engine running hours (hours)
I5.140: ECU: Engine running hours (seconds)
Electrical value (on generator set side)
I3.1.50: Frequency - Input1 - Reg #1
I3.1.55: U23 Line- to- line voltage - Input1 - Reg #1
I3.1.57: I1 Current - Input1 - Reg #1
I3.1.64: Total active power - Input1 - Reg#1
I3.1.68: Total reactive power - Input1 - Reg#1
I3.1.72: Total cosphi - Input1 - Reg #1
Figure 2-25 Saved Data
TP-7070 8/20
All of this information is saved according to 4 different
time periods:
10 minutes: record values every 1 second
4 hours: record values every 30 seconds
8 hours: record values every 1 minute
24 hours: record values every 3 minutes
Notes
Battery voltage 1
Battery current 1
Notes
On input U1 of regulation module 1
On input U1 of regulation module 1
On input U1 of regulation module 1
On input U1 of regulation module 1
On input U1 of regulation module 1
On input U1 of regulation module 1
Section 2 Operation