Location; Indoor Unit; Outdoor Unit; Pipe Length & Elevation Limits - Rinnai RINV34RC Installation Manual

Split type wall mounted air conditioner
Hide thumbs Also See for RINV34RC:
Table of Contents

Advertisement

LOCATION

INDOOR UNIT

Ensure the indoor unit is located away
from heat or steam�
Ensure the indoor unit is located so it can
be accessed for service and replacement�
Ensure the indoor unit is located so
condensate can be drained away�
Select a location where the indoor unit
can be securely mounted�
The
clearances
shown
maintained�

OUTDOOR UNIT

Select the location where exposure
to direct sunlight and strong wind are
minimised�
Select the location where the outdoor unit
can be securely mounted�
Select the location where the noise and
air flow will not cause nuisance.
Ensure there are no obstructions in the
air flow path.
Ensure the out door unit is located so
it can be accessed
replacement�
Do not place animals and plants near the
air discharge�
The
clearances
shown
maintained�
PIPE LENGTH & ELEVATION LIMITS
Models
mm
RINV25RC
Ø9.52
RINV34RC
Ø9.52
RINV51RC
Ø12.7
RINV70RC
Ø15.88
Rinnai
MUST
BE
for service and
MUST
BE
Pipe Size
Gas
Liquid
inch
mm
3/8
Ø6.35
3/8
Ø6.35
1/2
Ø6.35
5/8
Ø6.35
Indoor unit
Indoor unit
X
X
Y
Y
Outdoor unit
Outdoor unit
1 0 0 0
1 5 0
(All dimensions in mm)
Standard
Length
inch
m
1/4
5
1/4
5
1/4
5
1/4
5
Outdoor unit
Outdoor unit
X
X
Indoor unit
Indoor unit
8
1 5 0
3 0 0
0
1 0 0
Maximum
Maximum
Length - X
Height -Y
m
m
15
8
15
8
20
10
25
10
Y
Y
1 0 0
1 0 0
3 0 0
Additional
Refrigerant
g/m
20
25
30
40
Split AC IM