3.3

TECHNICAL FEATURES

• The chimney flue must be sealed from fumes.
• It must have a vertical run without narrowing. It must be realized with fume and condensation resistant materials with ther-
mal insulation and able to last against usual mechanical stresses.
It must be insulated to avoid condensation and to reduce fume cooling effects.
• The stove must be spaced out from fuels or flammable materials with an air gap or with insulating materials. Check the distan-
ce with the chimney manufacturer.
• The chimney entrance must be placed in the same room where the appliance is installed or otherwise in the adjacent room
and it must be provided with a solid and condensation collection chamber under the entrance, accessible through the sealed
metal gate.
• Auxiliary exhaust fans cannot be installed neither along the chimney nor on the chimney pot.
• The inner section of the chimney flue can be round (the best one) or square and the jointed sides must have a minimum radius
of 20 mm.
• The section dimension must be:
• minimun Ø100 mm
• recommended max Ø180 mm
• Made the efficiency of the chimney flue overhauled by an expert stove-repairer and if necessary cover the chimney flue with
materials in compliance with current regulations.
• The flue system must be placed on the roof.
• The chimney flue must be provided CE in accordance with EN 1443 regulation. Please find attached an example of label:
STUFE A PELLET
Fig. 3 - Inclined roof
LEGEND
Fig. 3
1
Height over the ridge of the roof = 0,5 mt
2
Roof inclination ≥ 10°
3
90°
4
Measured distance at 90° from the roof surface = 1,3 mt