Required Accessories; S-Bus Connection - Bosch Rexroth IndraControl S67 Manual

Digital module high speed 4 inputs/outputs – 0.2 a (4×m12)
Hide thumbs Also See for Rexroth IndraControl S67:
Table of Contents

Advertisement

36/79
Bosch Rexroth AG
Connecting Data and Supply Cable
6.2

Required Accessories

6.3

S-BUS Connection

Rexroth IndraControl S67 Digital Module High Speed 4 Inputs/Outputs – 0.2 A (84×M12)
The Bosch Rexroth accessory components listed below are required for con‐
necting the data and supply cable. The associated order numbers are listed
in
chapter 13 "Accessories" on page
S-BUS M12 terminator, IP67 degree of protection
S-BUS and supply cables, ready-made on both ends, IP67
Protective caps
The S-BUS is used for communication between a fieldbus coupler and the
connected IndraControl S67 components.
Requirement:
A Bosch Rexroth S-BUS cable ready-made on both ends is available,
which is necessary for optimal signal transmission.
The S-BUS terminator is available, which is necessary for communica‐
tion.
The following table outlines the assignment of the S-BUS connections:
Connection
OUT
IN
4
4
1
5
3
3
5
2
2
Tab. 6-1:
S-BUS: Pin assignment
To connect the S-BUS cable to the fieldbus coupler and to the modules, pro‐
ceed as follows:
1. Disconnect the power supply from those devices on which you have
mounted the S67-DIO4-HS-M12 module.
2. Connect the S-BUS cable (S1) to the OUT connection
fieldbus coupler and the IN connection
module. For example, if two modules have been connected to the field‐
bus coupler, connect the S-BUS cables (S1, S2) to the associated IN
and OUT connections, as shown in the figure below.
3. Tighten the plugs and sockets using the knurled-head screw.
4. Attach the S-BUS terminator (T) to the last I/O module as shown in the
figure and tighten the S-bus terminator.
DOK-CONTRL-S67DIO4M12H-AP02-EN-P
69.
Contact
Description
IN
1
RD+
2
RD-
3
TD-
1
4
TD+
5
0 V DC
Connection
Shielded
thread
(1) of the S67-DIO4-HS-M12
OUT
TD+
TD-
RD-
RD+
(3) of the

Advertisement

Table of Contents
loading

Table of Contents