DOK-CONTRL-S67DIO4M12H-AP02-EN-P
Rexroth IndraControl S67 Digital Module High Speed 4 Inputs/Outputs – 0.2 A (84×M12)
Position
LED
Color/status
15
SB
Green, flashing,
1 Hz
Green, flashing,
2 Hz
Position
LED
Color/status
16
F
Red
17
I/O
Yellow
Red
Position
LED
Color/status
18
U
Green
A
Off
19
U
Green
LS
Off
Cause
The module is in HOLD state
The module is in STOP state
Tab. 11-1:
Operational message 1
Cause
At least one global
diagnostic message was reported
at the module
Input and output signal active
Error at output
Tab. 11-2:
Operational message 2
Cause
Sensor/actuator supply U
ble
Sensor/actuator supply U
available
Logic supply U
LS
Logic supply U
LS
Tab. 11-3:
Operational message 3
Bosch Rexroth AG
Diagnostics via LED Signals
Remedy/Information
Is initiated by the field bus coupler.
In DI mode, the last input values
transmitted to the field bus coupler
are held in the process image
In DO mode, the output values are
held
Is initiated by the field bus coupler.
In DI mode, the input values in the
process image are set "0".
In DO mode, "0" is output as an
output value
Remedy/Information
Check the supply voltages U
U
of the upstream IndraControl
A
S67 components. For more infor‐
mation, see
tic Overview" on page 43
–
Inspect the actuator connection for
short circuits/overload. A short cir‐
cuit or an overload can only be di‐
agnosed when the output is switch‐
ed on
Remedy/Information
availa‐
–
A
not
Connect the supply voltage and
A
check the voltage level, if applica‐
ble.
is present
–
is not present
Connect the supply voltage and
check the voltage level, if applica‐
ble.
65/79
and
LS
chapter 8.2 "Diagnos‐