Subnet, or Gateway does not match the configured device of the same Device Name
residing on the selected LAN.
device residing on the selected LAN. Either there is no such Device Name configured in the
system, or the device with that Device Name resides on a different LAN.
Figure 88: List of Device Names on LAN with Status Indications
If the Device Name of the device on the network is not correct, select the target device in
the list of networked devices, and click Edit Device. This will open a new dialog that can be
used to set various parameters, including Device Name, directly on the device.
Note:
3.11
After the Configuration is Stored to the RX3i
CPU
The configuration is stored to the RX3i CPU using Machine Edition. For complete
instructions, refer to the PACSystems system documentation. If the configuration is stored
to non-volatile memory or is battery-backed, the CPU maintains configuration data over
power cycles.
The RX3i CPU transfers configuration data to the PROFINET Controller.
Configuration
indicates that the Device Name of the actual device matches, but the IP Address,
indicates that the Device Name of the actual device does not match any configured
For the PROFINET Controller to successfully deliver configuration to a device, only the
Device Name is required to match the configuration.