RSTI-EP PROFINET I/O Controller User Manual
GFK-2571R
3.1.2
For the embedded PROFINET Controller
CPE100/CPE115, it is not recommended to use
Update Rates below 16ms even though it is
configurable using Machine Edition.Basic
Configuration Steps
The basic configuration steps, described in this chapter, are:
In the hardware configuration, configure LAN2 as an embedded PROFINET LAN, or, for
slot-mounted hardware, add a PNC001 module to the RX3i main rack. This
automatically associates a LAN with the PROFINET Controller.
Configure the parameters of the PROFINET Controller itself.
Select the PROFINET Controller and add IO-Devices to its LAN. These IO-Devices can be
VersaMax PNS modules or third-party IO-Devices. Third-party IO-Devices and VersaMax
PNS modules use GSDML files to describe their capabilities. PAC Machine Edition
imports these GSDML files and incorporates the devices into the configuration.
Configure the parameters of the VersaMax PNS modules and third-party IO Devices.
Using the Machine Edition Inspector pane, configure the communications properties of
the PROFINET Controller and any attached RX3i PNS modules, VersaMax PNS modules,
and/or third-party IO Devices.
Add supported RX3i modules to the RX3i PNS remote nodes.
Add supported VersaMax modules to the VersaMax PNS remote nodes.
Configure the parameters of the RX3i I/O modules, VersaMax I/O modules and third-
party sub-modules in the remote nodes.
When the configuration is ready, use the Discovery and Configuration Protocol (DCP)
tool in Machine Edition to assign a Device Name to each IO-Device so the PROFINET
Controller can connect to the devices and deliver their configuration.
Store the configuration data from the programmer to the RX3i CPU.
Configuration Notes for Slot-Mounted PNC001
In the PAC Machine Edition hardware configuration, add a PNC001 to the RX3i main rack.
This automatically creates a LAN for the PNC001.
Configuration Notes for Embedded PROFINET IO-Controller
When LAN2 is configured for Ethernet, the corresponding ports support SRTP Client/Server,
Modbus TCP Client/Server, OPC UA Server, and EGD. All PROFINET controller services
(Including Explore PROFINET Networks) are disabled when LAN2 is configured for Ethernet.
Configuring LAN2 for PROFINET retains standard Ethernet operation and enables PROFINET
controller services.