Module Installation

RX3i rack power may be off or on (see Hot Insertion and Removal for details).
Holding the module firmly, align the module with the correct slot and connector.
Engage the module's rear pivot hook in the notch on the top of the backplane (1).
Swing the module down (2) until the module's connector engages the backplane's
backplane connector, and the release lever (PNC001-Ax only) on the bottom of the
module snaps into place in the bottom module retainer (3).
Visually inspect the module to be sure it is properly seated.
PNC001-Ax: Tighten the heat sink screw on the front of the module in the threaded hole
in the back plate to 6 in-lbs (0.68 Nm), using a flat-tip screwdriver.
PNC001-Bxxx: Secure the bottom of the module to the backplane using the two captive
Phillip's head machine screws provided with the module (not shown in diagram).
Figure 19: Install Module into RX3i Backplane
Installation
Section 2
May 2021
31