RSTI-EP PROFINET I/O Controller User Manual
GFK-2571R
2.4
Module Installation
•
RX3i rack power may be off or on (see Hot Insertion and Removal for details).
•
Holding the module firmly, align the module with the correct slot and connector.
•
Engage the module's rear pivot hook in the notch on the top of the backplane (1).
•
Swing the module down (2) until the module's connector engages the backplane's
backplane connector, and the release lever (PNC001-Ax only) on the bottom of the
module snaps into place in the bottom module retainer (3).
•
Visually inspect the module to be sure it is properly seated.
•
PNC001-Ax: Tighten the heat sink screw on the front of the module in the threaded hole
in the back plate to 6 in-lbs (0.68 Nm), using a flat-tip screwdriver.
•
PNC001-Bxxx: Secure the bottom of the module to the backplane using the two captive
Phillip's head machine screws provided with the module (not shown in diagram).
Figure 19: Install Module into RX3i Backplane
Installation
Section 2
May 2021
31