Figure 29. Attachment brackets

Model 1164-95X rear door heat exchanger

Learn about the specifications of the 1164-95X rear door heat exchanger (feature code EC05).
Water specifications
v Pressure
– Normal operation: <137.93 kPa (20 psi)
– Maximum: 689.66 kPa (100 psi)
v Volume
– Approximately 9 liters (2.4 gallons)
v Temperature
– Water temperature must be above the dew point in the data center
– 18°C ± 1°C (64.4°F ± 1.8°F) for ASHRAE Class 1 Environment
– 22°C ± 1°C (71.6°F ± 1.8°F) for ASHRAE Class 2 Environment
v Required water flow rate (as measured from the supply entrance to the heat exchanger)
– Minimum: 22.7 liters (6 gallons) per minute
– Maximum: 56.8 liters (15 gallons) per minute
Hardware specification sheets
65