Table 75. Dimensions for rack-mounted expansion unit
Weight (with drives
installed)
21.8 kg (48.0 lb)
Table 76. Electrical
Electrical characteristics
1
kVA (maximum)
Rated voltage and frequency
Thermal output (maximum)
Power requirements (maximum)
Phase
1
All measurements are made in conformance with ISO 7779 and declared in conformance with ISO 9296.
Table 77. Temperature requirements
Operating
10°C - 38°C (50°F - 100.4°F)
1
The maximum 38°C (100.4°F) temperature must be derated 1°C (1.8 °F) per 137 m (450 ft) above 1295 m (4250 ft).
Table 78. Environmental requirements
Environment
Noncondensing humidity
Wet bulb temperature
Safety compliance: This hardware is designed and certified to meet the following safety standards: UL
60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all national differences
Related information:
Acoustics
5888 PCIe storage enclosure
EDR1 expansion unit
Hardware specifications provide detailed information for your expansion unit, including dimensions,
electrical, power, temperature, environment, and service clearances.
Table 79. Dimensions for rack-mounted expansion unit
Weight (with drives
installed)
21.8 kg (48.0 lb)
Table 80. Electrical
Electrical characteristics
1
kVA (maximum)
Rated voltage and frequency
32
Site and hardware planning
Width
444.5 mm (17.5 in.)
1
1
Operating
20% - 80% (allowable)
40% - 55% (recommended)
21°C (69.8°F)
Width
444.5 mm (17.5 in.)
Depth (including front
bezel)
762 mm (30 in.)
Properties
0.46
100 - 127 V ac or 200 - 240 V ac at 50 - 60 Hz
1501 Btu/hr
440 W
1
Nonoperating
-40°C to 60°C (-40°F to 140°F)
Nonoperating
8% - 80% (including
condensing)
27°C (80.6°F)
Depth (including front
bezel)
762 mm (30 in.)
Properties
0.46
100 - 127 V ac or 200 - 240 V ac at 50 - 60 Hz
Height (with support rails)
44.5 mm (1.75 in.)
Maximum altitude
2134 m (7000 ft) above sea
level
Height (with support rails)
44.5 mm (1.75 in.)