Table 80. Electrical (continued)
Electrical characteristics
Thermal output (maximum)
Power requirements (maximum)
Phase
1
All measurements are made in conformance with ISO 7779 and declared in conformance with ISO 9296.
Table 81. Temperature requirements
Operating
10°C - 38°C (50°F - 100.4°F)
1
The maximum 38°C (100.4°F) temperature must be derated 1°C (1.8 °F) per 137 m (450 ft) above 1295 m (4250 ft).
Table 82. Environmental requirements
Environment
Noncondensing humidity
Wet bulb temperature
Safety compliance: This hardware is designed and certified to meet the following safety standards: UL
60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all national differences
Rack specifications
Rack specifications provide detailed information for your rack, including dimensions, electrical, power,
temperature, environment, and service clearances.
For non-IBM rack specifications, see Rack installation procedures for racks not purchased at IBM.
Select your rack model to view its specifications.
Related reference:
"Rack installation specifications for racks not purchased from IBM" on page 73
Learn the requirements and specifications for installing IBM systems into racks that were not purchased
from IBM.
0550 model 9406-830 rack
Rack specifications provide detailed information for your rack, including dimensions, electrical, power,
temperature, environment, and service clearances.
1
1
Operating
20% - 80% (allowable)
40% - 55% (recommended)
21°C (69.8°F)
Properties
1501 Btu/hr
440 W
1
Nonoperating
-40°C to 60°C (-40°F to 140°F)
Nonoperating
8% - 80% (including
condensing)
27°C (80.6°F)
Maximum altitude
2134 m (7000 ft) above sea
level
Hardware specification sheets