Voltage Protection Module (VPM)
6.7 Electrical connection
For operation on a High Frequency Drive, also observe the following:
• There can be only one spur line to the Voltage Protection Module.
• Three ferrite rings are applied to each motor cable (type: EPCOS/TDK B64290L0022X065).
• The shrink tubing used must be suitable for temperatures of up to 135 °C, at least.
An installation sequence for individual conductors is outlined below. It is particularly relevant for
larger cross-sections.
Preparation
The following preparations must be made before setting up connections:
• Loosen the 4 screws on the cover of the housing, so that the cover can be moved into the
cutouts.
• Move the enclosure cover to the point where the cutout widens out so it can be lifted over the
screw heads.
• Secure the cable glands for the signal cable and the power cables to the enclosure cable
entries of the Voltage Protection Module.
• Remove 300 mm of the cable sheath of the power cables and expose the shield to match the
enclosure gland being used.
• Remove the insulation at the ends of the individual conductors and attach cable lugs.
• Attach the signal cable to X3 and secure the cable with cable ties inside the Voltage
Protection Module.
6.7.1

Connecting signaling contact X3

The signaling contact X3 must be wired before connecting the power cables.
Figure 6-7
90
Cable tie
Signaling contact X3
Connection of the signaling contact using the VPM200 as an example
High Frequency Drive
System Manual, 10/2020, 6SL3097-5AH10-0BP0