5.3.1.2

Device nameplate (FM/CSA)

● For power demands see Curve 1 (General Purpose, Intrinsically Safe, Non-Sparking,
Non-incendive). (Page 190)
● For wiring requirements: follow local regulations.
● Approved dust-tight and water-tight conduit seals are required for outdoor Type 4X, Type
6, IP67, IP68 locations.
● Refer to Instructions specific to hazardous area installations (Page 34).
Note
Selecting a suitable PLC input module, power supply, or barrier requires knowledge about
Intrinsic Safety and the application. It is the responsibility of the installer to ensure that the
intrinsically safe installation complies with both the apparatus approval requirements and the
relevant national code of practice.
5.4

Instructions specific to hazardous area installations

5.4.1

(Reference European ATEX Directive 2014/34/EU, Annex II, 1.0.6)

The following instructions apply to equipment covered by certificate numbers SIRA
06ATEX2378X, SIRA 05ATEX1001X, and SIRA 09ATEX4151X:
1. For use and assembly, refer to the main instructions.
2. The equipment is certified for use as Category 1G equipment per SIRA 06ATEX2378X,
Category 1/2 equipment per SIRA 05ATEX1001X, and Category 3G equipment per SIRA
09ATEX4151X.
3. The equipment may be used with flammable gases and vapors with apparatus group IIC,
IIB, and IIA, and temperature classes T1, T2, T3, and T4.
4. The equipment is certified for use in an ambient temperature range of –40 °C to +80 °C.
5. The equipment has not been assessed as a safety related device (as referred to by
Directive 2014/34/EU Annex II, clause 1.5).
34
FM Intrinsically Safe connection drawing number A5E01003040 and CSA Intrinsically Safe
connection drawing number A5E01003039 can be downloaded from the product page of our
website at: www.siemens.com/LR200 (www.siemens.com/LR200). Go to Support > Installation