7.4.8

Power-on resets (4.8.)

The number of power cycles that have occurred since manufacture. In SIMATIC PDM, open
the menu View – Wear.
7.4.9

LCD fast mode (4.9.)

Description
Values
Factory setting
Note
• LCD Fast Mode takes effect only after 30 minutes of inactivity. (Each time the device is
powered up, a further 30 minutes of inactivity is required.)
• LCD Fast Mode affects Measurement mode only; it has no effect on Navigation mode.
7.4.10

LCD contrast (4.10.)

Description
Values
Factory setting
Note
Adjust the value to improve visibility in different temperatures and light conditions. Change
the value in small steps to ensure you can continue to read the display.
132
Enables a faster rate of measurement from the device by disabling most of the
display area. Only the bar graph will be refreshed when LCD Fast Mode is set to
ON.
ON or OFF
OFF
The factory setting is for optimum visibility at room temperature and in average
light conditions. Extremes of temperature will lessen the contrast.
Range: 0 (low contrast) to 20 (high contrast)
10
SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE