Operation
NO SERVICE
LEVEL
SPACE
DISTANCE
The point from which High and Low Calibration points are referenced: see Uni-construction
1)
polypropylene rod antenna (Page 152) and Dimension drawing (Page 152).
Low Calibration Point
Distance from Sensor Reference to Low Calibration Point: usually process empty level. [See
Operation (1.5.) for an illustration.]
Values
High Calibration Point
Distance from Sensor reference point to High Calibration Point: usually process full level.
[See Operation (1.5.) for an illustration.]
Values
Apply? (Apply changes)
In order to save the Quick Start settings, it is necessary to select Yes to apply changes.
Options
Press Mode
6.2.1.3

Auto False Echo Suppression

If you have a vessel with known obstructions, we recommend using Auto False Echo
Suppression to prevent false echo detection. See TVT setup (2.8.7.) (Page 115) for
instructions.
This feature can also be used if SITRANS LR200 displays a false high level, or the reading is
fluctuating between the correct level and a false high level.
SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
Description
Measurement and associated loop current are not updated, and the device defaults
to Fail-safe mode.
Distance to material surface referenced from Low Calibration Point
Distance to material surface referenced from High Calibration Point
Distance to material surface referenced from Sensor reference point
Range: 0.00 to 20.00 m
Range: 0.00 to 20.00 m
YES, NO, DONE (Display shows DONE when Quick Start is successfully com-
pleted.)
to return to Measurement mode. SITRANS LR200 is now ready to operate.
45