3.4.5 Channel X.Y (Parameterised for 2 Switching Outputs)

Table 1-5: Parameters on the "Channel X.Y" tabs
Designation
Timer functions
Dependence on object
"Central permanent
ON"
Dependence on object
"Central permanent
OFF"
Dependence on object
"Inhibit channels 1.X"
Behaviour after BUS
voltage loss
Behaviour after BUS
recovery*
Behaviour at mains
voltage recovery
without BUS voltage
Time base for staircase
timer
Factor for staircase
timer
1 ... 255 x Time base
As of: Apr-06 (Subject to change without notice)
Values
switch ON/OFF
staircase time switch with cut out
early warning
impulse function
ON / OFF delay
no
yes
no
yes
no
yes
unchanged
switch ON
switch OFF
unchanged
switch ON
switch OFF
trigger timer**
switch ON
remain OFF
restore previous relay state
Parameters for the staircase time switch
1 sec, 10 sec, 30 sec, 1 min
Keyboard input 1 to 255
theben
Description
Selection of a timer function from 4
options for each of the switching
outputs.
Is the Central permanent ON object
to switch this channel as well?
Is the Central permanent OFF
object to switch this channel as
well?
Is the inhibit object to have
influence over this channel?
Serves for taking on a defined
status after a bus failure,
This is important for consumers,
e.g. that must not continue
operation without control.
Similar to the previous row.
Important for consumers, e.g. that
must not start operating again
without control.
Refer to the rows above
To attain a maximum of flexibility,
the staircase lighting time is
calculated from a time base and a
factor
The staircase lighting time is equal
to the time base multiplied by the
factor.
Example:
Time base 10 s x factor 2 is
2 x 10 s = 20 s
As soon as this time has elapsed, a
cutout early warning is issued, i.e.
the light is switched off for 0.25 s
and then switched on again for 30s.
After this, the feedback is sent (obj.
1). (The cutout early warning
intervals (0.25 s and 30s) are
preprogrammed and cannot be
changed).
Page 20 of 36