The Parameters; General - Theben RMG 8 Manual

Switch actuator; switch actuator modules; blinds actuator
Table of Contents

Advertisement

Blinds and switch actuator RMG 8, blinds actuator JMG 4
and switch actuator module RME 8 - EIB

3.4 The Parameters

3.4.1 General

The "General" tab is used for setting the basic parameters.
The parameters that can be set are listed in the table below.
Table 1-1: Parameters on the "General" tab
Designation
Used device(s)
Device keys are
Manual mode
As of: Apr-06 (Subject to change without notice)
Values
only RMG 8
RMG 8 and RME 8
RMG 8 and RMX 4
always enabled
only enabled if theben-key for JMG
4 / RMG 8 (item no. 907 0 304) is
plugged
automatically cleared after 30 min
permanent !
theben
Description
Select whether only the basic
device (4 drives) or the basic device
+ an extension (a total of 8 or 6
drives) is/are available
Key lock deactivated
If the option "only enabled if key is
plugged" is selected, the device
keyboard is locked and manual
operation is possible only if a key is
inserted in the interface on the front
of the device.
Function of the "manual" button on
the device.
The time limit of 30 minutes
prevents a permanent disturbance of
the system if the "manual" button
was pressed e.g. by unauthorized
persons.
If a time limit is not selected, the
manual mode is exited only if the
following events occur:
the button is pressed once more
the bus voltage is restored
the mains voltage is interrupted
the device is reprogrammed
Page 16 of 36

Advertisement

Table of Contents
loading

Table of Contents