3.4 The Parameters
3.4.1 General
The "General" tab is used for setting the basic parameters.
The parameters that can be set are listed in the table below.
Table 1-1: Parameters on the "General" tab
Designation
Used device(s)
Device keys are
Manual mode
As of: Apr-06 (Subject to change without notice)
Values
only RMG 8
RMG 8 and RME 8
RMG 8 and RMX 4
always enabled
only enabled if theben-key for JMG
4 / RMG 8 (item no. 907 0 304) is
plugged
automatically cleared after 30 min
permanent !
theben
Description
Select whether only the basic
device (4 drives) or the basic device
+ an extension (a total of 8 or 6
drives) is/are available
Key lock deactivated
If the option "only enabled if key is
plugged" is selected, the device
keyboard is locked and manual
operation is possible only if a key is
inserted in the interface on the front
of the device.
Function of the "manual" button on
the device.
The time limit of 30 minutes
prevents a permanent disturbance of
the system if the "manual" button
was pressed e.g. by unauthorized
persons.
If a time limit is not selected, the
manual mode is exited only if the
following events occur:
•
the button is pressed once more
•
the bus voltage is restored
•
the mains voltage is interrupted
•
the device is reprogrammed
Page 16 of 36