Drives General - Theben RMG 8 Manual

Switch actuator; switch actuator modules; blinds actuator
Table of Contents

Advertisement

Blinds and switch actuator RMG 8, blinds actuator JMG 4
and switch actuator module RME 8 - EIB

3.4.2 Drives General

Table 1-2: Parameters on the "Drives general" tab
Designation
Security 1 – 3 (objects) without cyclical monitoring
Cyclical monitoring of
all 3 Objects 1 ... 255
[x 1min]
Allocation of the 0%
Position to the objects
Slats [%]
User level for drives
(Descriptions: refer to the chapter Expert Application).
As of: Apr-06 (Subject to change without notice)
Values
with cyclical monitoring
Input: 1 to 255
0% corresponds to travel down
position
0% corresponds to travel up position
Standard
Expert
Standard parameters for the "expert" user level
theben
Description
The last telegram always
determines the security status.
If a security object has been
assigned an important alarming
function, a check is performed
whether the alarm sensor sends data
periodically.
If the sender fails, the security
status is taken up.
Example (see below).
If the sensors connected to the
security objects send cyclically, the
cycle time, i.e. the time interval
between 2 telegrams must be
entered here.
Recommendation: The monitoring
time of the actuator must be twice
as long as the cycle time of the
device to be monitored.
Example:
If the air speed meter sends to the
security object 1 every 5 minutes,
set the monitoring time to 10
minutes.
Input of the reference position for
calculating the slats turn.
Only standard parameters for
standard use.
On the expert level, the blinds
actuator can be precisely adjusted
in relation to the drives. Thus,
utmost positioning accuracy can be
attained.
Page 17 of 36

Advertisement

Table of Contents
loading

Table of Contents